English
Language : 

MLY10.241 Datasheet, PDF (7/16 Pages) PULS GmbH – DC12-48V (120V), 10A, DUAL REDUNDANCY MODULE
MiniLine-2
MLY-Series
MLY10.241
DC12-48V (120V), 10A, DUAL REDUNDANCY MODULE
6. TERMINALS AND WIRING
Type
Solid wire
Stranded wire
American Wire Gauge
Max. wire diameter
Wire stripping length
Screwdriver
Recommended tightening torque
Input
screw terminals
0.5-6mm2
0.5-4mm2
20-10 AWG
2.8mm (including ferrule)
7mm / 0.275inch
3.5mm slotted or
Pozidrive No 2
1Nm, 9lb.in
Output
screw terminals
0.5-6mm2
0.5-4mm2
20-10 AWG
2.8mm (including ferrule)
7mm / 0.275inch
3.5mm slotted or Pozidrive
No 2
1Nm, 9lb.in
Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C and
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Screws of unused terminal compartments should be securely tightened.
e) Ferrules are allowed, but not required.
Apr. 2014 / Rev. 1.5 DS-MLY10.241-EN
All parameters are specified at 24V, 10A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
7/16