English
Language : 

CD5.241-S1 Datasheet, PDF (7/23 Pages) PULS GmbH – DC/DC Converter
CD-Series
CD5.241-S1
DC/DC Converter 24V, 5A
6. HOLD-UP TIME
The input side of the DC/DC converter is equipped with a bulk capacitor which keeps the output voltage alive for a
certain period of time when the input voltage dips or is removed. The bulk capacitor can be discharged by loading the
DC/DC converter on the output side or through a load which is parallel to the input. There is no protection in the
DC/DC converter which prevents current from flowing back to the input terminals. If prevention is needed, an external
diode should be used.
Hold-up Time
typ.
11.8ms
input 24Vdc, output: 24Vdc, 2.5A, see Fig. 6-1
typ.
6ms
input 24Vdc, output: 24Vdc, 5A, see Fig. 6-1
Fig. 6-1 Hold-up time vs. input voltage
Hold-up Time
12ms
10
(a) (b)
8
(c)
6
(d)
4
2
0
18
Input Voltage
(a) 24V, 2.5A, typ.
(b) 24V, 2.5A, min.
(c) 24V, 5A, typ.
(d) 24V, 5A, min.
20
22 24 26 28Vdc
Fig. 6-2 Shut-down test setup
S1
+
DC
Source
-
DC/DC
Converter
Input +
CD5
Output -
+
Load
-
Fig. 6-3 Shut-down behavior, definitions
Intput
Voltage
S1 opens
Output
Voltage
Hold-up Time
- 5%
Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on during this time.
Mar. 2016 / Rev. 1.5 DS-CD5.241-S1-EN
All parameters are specified at 24V, 5A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/23