QS10.DNET Datasheet, PDF (5/22 Pages) PULS GmbH – 24V, 8A, DEVICENET POWER SUPPLY
Q-Series
QS10.DNET
24V, 8A, DEVICENET® POWER SUPPLY
4. DC-INPUT
DC input
DC input range
DC input current
Allowed Voltage L/N to Earth
Turn-on voltage
Shut-down voltage
nom.
min.
typ.
max.
typ.
typ.
DC 110-150V
88-187Vdc
1.9A
375Vdc
80Vdc
55Vdc
-20%/+25%
continuous operation
110Vdc, at 24V, 8A
continuous, IEC 62103
steady state value
steady state value
Fig. 4-1 Wiring for DC Input
Battery
Power Supply
+
AC
L
N
+
PE
-
Load
-
DC
Instructions for DC use:
a) Use a battery or similar DC source.
For other sources contact PULS
b) Connect +pole to L and –pole to N.
c) Connect the PE terminal to a earth wire or to the machine
ground.
5. INPUT INRUSH CURRENT
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short
input voltage interruptions.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Inrush current
Inrush energy
Inrush delay (A)
max.
typ.
max.
typ.
AC 100V
10Apeak
5Apeak
4A2s
650ms
AC 120V
10Apeak
4Apeak
4A2s
520ms
AC 230V
10Apeak
7Apeak
4A2s
250ms
over entire temperature range
over entire temperature range
over entire temperature range
see (A) in Fig. 5-1
Fig. 5-1 Input inrush current, typical behavior
A
Input Current
Input Voltage
Output Voltage
A….
Inrush delay
Input:
Output:
Ambient:
Upper curve:
Middle curve:
Lower curve:
Time basis:
230Vac
24V, 8A
25°C
Input current 2A / DIV
Input voltage 500V / DIV
Output voltage 20V / DIV
100ms / DIV
Dec. 2014 / Rev. 2.2 DS-QS10.DNET-EN