24V, 8A, DEVICENET® POWER SUPPLY
POWER SUPPLY
ƒ AC 100-240V Wide-range Input
ƒ DeviceNet® Approved
ƒ NEC Class 1 Compliant
ƒ Width only 60mm
ƒ Efficiency up to 93.4%
ƒ Active Power Factor Correction (PFC)
ƒ Negligible low Inrush Current Surge
ƒ Short-term Operation down to 60Vac and up to 300Vac
ƒ Full Power Between -25°C and +60°C
ƒ DC-OK Relay Contact
ƒ Quick-connect Spring-clamp Terminals
ƒ 3 Year Warranty
GENERAL DESCRIPTION
The QS10.DNET power supply is a derivate of the
Dimension QS10 family, which is specially designed to
meet the DeviceNet® requirement. The QS10.DNET exists
beside the QS5.DNET, which is the right choice to supply
networks that use NEC Class 2 cables.
The specialties of DeviceNet® power supplies are:
ƒ The nominal and overload currents are sized for the
ratings of the DeviceNet® cables.
ƒ Large load capacitors can be charged in a very short
period of time.
ƒ After turn on, the output voltage increases according
to the DeviceNet® timing specification.
ƒ The upper level of the output level is limited to protect
the network.
The most outstanding features are a high efficiency,
compact size, wide-range input voltage, a very low
inrush surge and a DC-ok contact. High immunity to
transients and power surges and a low electromagnetic
emission makes usage in nearly every environment
possible.
Unique quick-connect spring-clamp terminals allow a
safe and fast installation. A large international approval
package makes this unit suitable for nearly every
situation.
ORDER NUMBERS
Power Supply QS10.DNET 24V Power supply
Accessory
ZM1.WALL
ZM13.SIDE
UF20.241
Wall mount bracket
Side mount bracket
Buffer unit
SHORT-FORM DATA
Output voltage
DC 24V
Adjustment range 24 – 24.5V
Output current
8A
Output power
192W
Output ripple
< 50mVpp
Input voltage
AC 100-240V
Mains frequency 50-60Hz
AC Input current 1.77 / 1.0A
Power factor
0.98 / 0.92
AC Inrush current typ. 4 / 7A peak
Efficiency
92.8 / 93.4%
Losses
14.9 / 13.6W
Temperature range -25°C to +70°C
Derating
5W/°C
Hold-up time
typ. 33 / 34ms
Dimensions
60x124x117mm
20Hz to 20MHz
±15%
±6%
at 120 / 230Vac
at 120 / 230Vac
at 120 / 230Vac
at 120 / 230Vac
at 120 / 230Vac
operational
+60 to +70°C
at 120 / 230Vac
WxHxD
MARKINGS
IND. CONT. EQ.
UL 508
UL 60950-1
Class I Div 2
Marine
EMC, LVD
Dec. 2014 / Rev. 2.2 DS-QS10.DNET-EN
All parameters are specified at 24V, 8A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany