YR40.242 Datasheet, PDF (16/17 Pages) PULS GmbH – DUAL REDUNDANCY MODULE
Y-Series
YR40.242
12-28V, 40A, DUAL REDUNDANCY MODULE
17.4. 1+1 REDUNDANCY UP TO 20A
1+1 Redundancy up to 20A requires two 20A power supplies and one YR40.242 redundancy module.
Fig. 17-1 Wiring diagram, 1+1 Redundancy, 20A output current
20A
Load
Failure
Monitor
Power
Supply
DC-OK
+-
Output
YR40.242
Redundancy
Module
Power
Supply
DC-OK
L N PE + + - -
Input Input
12
+-+-
L N PE + + - -
I
I
L
N
PE
Note: Use separate mains systems for each power supply whenever it is possible
17.5. N+1 REDUNDANCY, EXAMPLE WITH 60A
N+1 Redundancy up to 60A requires four 20A power supplies and two YR40.242 redundancy modules.
Fig. 17-2 Wiring diagram, n+1 Redundancy, 60A output current
60A
Load
Failure
Monitor
DC-OK
Power
Supply
+-
Output
YR40.242
Redundancy
Module
Power
Supply
DC-OK
L N PE + + - -
Input Input
12
+-+-
L N PE + + - -
DC-OK
Power
Supply
+-
Output
YR40.242
Redundancy
Module
Power
Supply
DC-OK
L N PE + + - -
Input Input
12
+-+-
L N PE + + - -
I
I
I
I
L
N
PE
Note: Use separate mains systems for each power supply whenever it is possible
Apr. 2014 / Rev. 1.1 DS-YR40.242-EN