English
Language : 

YR40.242 Datasheet, PDF (1/17 Pages) PULS GmbH – DUAL REDUNDANCY MODULE
Y-Series
YR40.242
12-28V, 40A, DUAL REDUNDANCY MODULE
MOSFET REDUNDANCY MODULE
ƒ For N+1 and 1+1 Redundant Systems
ƒ Dual Input with Single Output
ƒ Suitable for all DIMENSION Power Supplies
Except QT20 and QTD20 Series
ƒ Only 72mV Voltage Drop at 20A Output Current
ƒ Only 1.7W Loss at 20A and 5.9W at 40A Output Current
ƒ 160% (65A) Peak Load Capability
ƒ Reverse Input Polarity Protection
ƒ Full Power Between -40°C and +60°C
ƒ Width only 36mm
ƒ Rugged Metal Housing
ƒ Easy Wiring:
Distribution Terminal for Negative Pole Included
ƒ 3 Year Warranty
GENERAL DESCRIPTION
The YR40.242 is a redundancy module, which can be
used to build 1+1 and N+1 redundant systems. It is
equipped with two input channels, which can be
connected to power supplies with up to 20A output
current and one output, which can carry nominal
currents up to 40A. In addition to the YR40.242, the
YR40.241 is also available. This unit has an additional
circuit included, which generates a supply voltage for
the internal mosfets even when the output of the unit is
in a short circuit condition. This makes the unit suitable
for any power supplies.
The novelty of this redundancy module is the utilization
of mosfets instead of diodes for the decoupling of the
two input channels. This reduces the heat generation
and the voltage drop between input and output. The
redundancy module does not require an additional
auxiliary voltage.
Due to the low power losses, the unit is very slender and
only requires 36mm width on the DIN-rail. Large
connection terminals allow for a safe and fast
installation. The large international approval package
makes this unit suitable for nearly every application.
ORDER NUMBERS
Redundancy YR40.242
Module
Accessory
ZM2.WALL
ZM11.SIDE
12-28V Standard unit
Wall/ panel mount
bracket
Side mount bracket
SHORT-FORM DATA
Input voltage
DC 12-28V
±30%
Input voltage range 8.4-36.4Vdc
Input current
2x 0-20A
continuous
2x 20-32.5A for 5 seconds
Output current
0-40A
continuous
40-65A
for 5 seconds
max. 26A
in overload*) or
short circuit mode
Input to output
typ. 72mV
input: 2x10A
voltage drop
typ. 112mV input: 1x20A
typ. 140mV input: 2x20A
Power losses
typ. 230mW at no load
typ. 1.7W
input: 2x10A
typ. 2.4W
input: 1x20A
typ. 5.9W
input: 2x20A
Temperature range -40°C to +70°C operational
Derating
1A/°C (output) +60 to +70°C
Dimensions **)
36x124x127mm WxHxD
Weight
280g, 0.62lb
*) Currents at voltages below 6V
**) Plus 4mm in depth for the screw terminal
MARKINGS
IND. CONT. EQ.
UL 508
UL 60950-1
IECEx
ATEX
II 3G Ex nA IIC T4 Gc
Marine
Class I Div 2
EMC, LVD
Apr. 2014 / Rev. 1.1 DS-YR40.242-EN
All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted
www.pulspower.com Phone +49 89 9278 0 Germany
1/17