19. APPROVALS
EC Declaration of Conformity
DeviceNet®
IEC 60950-1
2nd Edition
UL 508
UL 60950-1
2nd Edition
ANSI / ISA 12.12.01-2007
(Class I Div 2)
Marine
SEMI F47
GOST P
The CE mark indicates conformance with the EMC directive
2004/108/EC, the low-voltage directive (LVD) 2006/95/EC and
the RoHS directive 2011/65/EC.
DeviceNet conformance tested by the Open DeviceNet®
Vendor Organization.
CB Scheme,
Information Technology Equipment
IND. CONT. EQ.
Listed for use as Industrial Control Equipment;
U.S.A. (UL 508) and Canada (C22.2 No. 107-1-01);
E-File: E198865
Recognized for use as Information Technology Equipment,
Level 5; U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950-1);
E-File: E137006
Recognized for use in Hazardous Location Class I Div 2 T4
Groups A,B,C,D systems; U.S.A. (ANSI / ISA 12.12.01-2007)
and Canada (C22.2 No. 213-M1987)
The unit is suitable for use in Class I Division 2 Groups A, B, C, D locations.
Substitution of components may impair suitability for Class I Division 2 environment.
Do not disconnect equipment unless power has been switched off. Wiring must be in
accordance with Class I, Division 2 wiring methods of the National Electrical Code,
NFPA 70, and in accordance with other local or national codes.
GL (Germanischer Lloyd) classified and
ABS (American Bureau for Shipping) PDA
Environmental category: C, EMC2
Marine and offshore applications
SEMI F47-0706
Ride-through compliance for semiconductor industry.
Full SEMI range compliance
(Input: AC120V or higher, output: < 91.2W)
Certificate of Conformity for Russia and other GUS countries
20. FULFILLED STANDARDS
EN 61558-2-17
EN/IEC 60204-1
EN/IEC 61131-2
EN 50178, IEC 62103
Safety of Power Transformers
Safety of Electrical Equipment of Machines
Programmable Controllers
Electronic Equipment in Power Installations
Mar. 2013 / Rev. 2.2 DS-QS5.DNET-EN
All parameters are specified at 24V, 3.8A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany