English
Language : 

CS10.241 Datasheet, PDF (10/26 Pages) PULS GmbH – SINGLE PHASE INPUT
C-Line
CS10.241, CS10.241-S1
24V, 10A, SINGLE PHASE INPUT
8. EFFICIENCY AND POWER LOSSES
AC 100V
AC 120V
AC 230V
Efficiency
typ.
90.7%
91.0%
91.6% at 24V, 10A
typ.
90.0%
90.7%
91.2%
at 24V, 12A (Power Boost)
Average efficiency*)
typ.
90.5%
90.2%
91.0%
25% at 2.5A, 25% at 5A,
25% at 7.5A. 25% at 10A
Power losses
typ.
5.8W
8.4W
7.5W
at 24V, 0A
typ.
12.0W
12.3W
11.3W at 24V, 5A
typ.
24.6W
23.7W
22.0W at 24V, 10A
typ.
31.9W
29.6W
27.9W
at 24V, 12A (Power Boost)
*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.
Fig. 8-1 Efficiency vs. output current at 24V,
typ
Efficiency
92%
(c)
91
(b)
(a)
90
(a) 100Vac
(b) 120Vac
(c) 230Vac
89
88
2
Output Current
4
6
8
10 12A
Fig. 8-3 Efficiency vs. input voltage at 24V,
10A, typ.
Efficiency
92%
91
90
89
88
85
Input Voltage
120 155 190 225 260Vac
Fig. 8-2 Losses vs. output current at 24V, typ.
Power Losses
32W
28
24
20
16
12 (a) (b)(c)
8
4
0
02
(a)
(b)
(c)
(a) 100Vac
(b) 120Vac
(c) 230Vac
Output Current
4 6 8 10 12A
Fig. 8-4 Losses vs. input voltage at 24V, 10A,
typ.
Power Losses
27W
24
21
18
15
12
9
85
Input Voltage
120 155 190
225 260Vac
Jul. 2015 / Rev. 2.0 DS-CS10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
10/26