English
Language : 

UZK24.121 Datasheet, PDF (1/9 Pages) PULS GmbH – BATTERY MODULE
U-Series
UZK24.121, UZO24.121
BATTERY MODULE 24V, 12AH
PASSIVE BATTERY MODULE
ƒ 24V, 12Ah Battery Capacity
(2x 12V Batteries in Series)
ƒ IP00 Open Type Protection Level
ƒ Small Mounting Footprint
ƒ ATO Fuse for Power Wires Included
ƒ 2m Power Leads Included
ƒ PT1000 Sensor for Battery Module Temperature
Included
ƒ Center-tap Terminal with Auto-resettable Fuse
Included to Support the PULS 1-Battery-Concept
1. GENERAL DESCRIPTION
The UZK24.121 passive battery module utilizes two non-
spillable maintenance-free lead-acid batteries
(connected in series), that are assembled in one package
with all the required wiring included.
The battery module includes the monitoring and
protection board UZS24.100. This board contains a
temperature sensor and a center-tap connection with
an auto-resettable fuse to protect the center-tap wire
between the battery module and the DC-UPS control
unit. Connecting the center-tap wire to the DC-UPS
control unit enables all the benefits of the PULS 1-
Battery-Concept. This makes the use of matched
replacement batteries unnecessary and allows a precise
battery charging and testing which results in the
longest possible battery life.
The UZK24 battery module is available in two different
options. It can be ordered with assembled batteries or
as a battery bracket without batteries, allowing for
different battery options. The mounting bracket option
also allows the batteries to be assembled just in time,
avoiding outdated batteries due to limited shelf life.
3. ORDER NUMBERS
Battery Module UZK24.121
UZO24.121
Replacement UZB12.121
Battery module with
assembled batteries
Battery module without
assembled batteries
Battery replacement
12V, 12Ah 2pcs needed
for one battery module
2. DATA
Battery type
Battery design life
Battery voltage
Battery capacity
Battery current
Battery fuse
Temperature sensor
Charging voltage
Self-discharge rate
Temperature range
Dimensions
Weight
VRLA
Lead-acid
3 to 5 years
acc. EUROBAT
DC 24V
12Ah
max. 35A
for discharging
max. 3.5A
for charging
35A
ATO fuse
PT1000
27.8V
at 10°C
27.5V
at 20°C
27.15V
at 30°C
26.8V
at 40°C
3%/month
at 20°C
-10°C to +40°C for charging
-15°C to +50°C for discharging
-20°C to +50°C for storage
203x186x143mm WxHxD
9000g / 19.8lb UZK24.121
900g / 2lb
UZO24.121
4. MARKINGS
IND. CONT. EQ.
UL 60950-1,
UL 508, pending
pending
LVD
Jul. 2014 / Rev. 1.2 DS-UZK24.121-EN
All parameters are specified at, 25°C ambient temperature unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/9