0912034 Datasheet, PDF (2/5 Pages) PHOENIX CONTACT – Electronic device circuit breaker - ECP 4
https://www.phoenixcontact.com/us/products/0912034
Electronic device circuit breaker - ECP 4 - 0912034
Technical data
General
Overvoltage category
Insulating material
Flammability rating according to UL 94
Electrical data
Fuse
Fuse type
Rated surge voltage
Operating voltage
Nominal current IN
Required backup fuse
Dielectric strength
Degree of pollution
Overvoltage category
Insulating material group
Switching capacity ICN
Closed circuit current I0
Dimensions
Height
Width
Depth
Height NS 35/7,5
Height NS 35/15
Complete module height
Complete module width
Complete module depth
Ambient conditions
Degree of protection
Ambient temperature (operation)
Connection data
Connection method
II
PPS
V0
Electronic
Automatic device
0.5 kV
24 V DC
18 V DC ... 32 V DC
4A
not required, integrated failsafe element
1000 V AC (Actuation area)
500 V AC (Installation area)
500 V AC (Load circuit signal contact)
2
II
IIIa
Active current limitation
typ. 13 mA
60 mm
12.5 mm
70 mm
144 mm
151.5 mm
115 mm
38 mm
147.5 mm
IP30 (Actuation area)
0 °C ... 50 °C (non-condensing)
Screw connection
Drawings
08/01/2016 Page 2 / 5