English
Language : 

E5CK Datasheet, PDF (9/22 Pages) Omron Electronics LLC – Advanced, Compact Digital Controllers
Wiring
Terminal Arrangement
AC100−240V~
(AC/DC24V~)
SOURCE
SUB1
OUT1
5 11 12 10
4
9
3
8
2
7
1
13 14
6
OUT2
IN
OPTION
Precautions
Use ducts to separate input leads and power lines in order to protect
the Controller and its lines from external noise.
Solderless terminals are recommended when wiring the Controller.
Tighten the terminal screws using a torque no greater than 0.78 N·m,
or 8 kgf·cm max. Take care not to tighten the terminal screws too
tightly.
Power Blocks
The E5CK has independent power supplies for each of the terminal
blocks shown below. However, note that the power supplies for
blocks C (exclude relay output) and D are shared for the following
option unit.
• Option unit: E53-CKB or E53-CKF
A
C
5 11 12 10
4
9
C
3
2
8
7
1 13 14 6
D
B
Wiring
Power Supply
Input 100 to 240 VAC or AC/DC 24 V to terminal numbers 4 and 5 according to the specification.
5
11 12 10
4
9
3
8
2
7
1
13 14
6
Input
Connect the input to terminal numbers 6 to 8 as follows according to the input type.
5 11 12 10
4
9
3
8
2
7
1
13 14
6
8
−
7
6
+
Thermocouple
8
7
6
Platinum resistance
thermometer
8
−
7
V
6
+
Voltage input
8
−
7
mA
6
+
Current input
TC⋅PT
V
I
Match the inputs with the internal jumper settings for each input type. For thermocouple or platinum resistance thermometer inputs, set the inputs
to a common position (TC/PT) as the temperature input.
Control Output
Terminal numbers 11 and 12 are for control output 1 (OUT1). The five output types and internal equalizing circuits are available according to the
Output Unit.
5
11 12 10
4
9
3
8
2
7
1
13 14
6
11
12
Relay
E53-R4R4
+
+v 11
+
+v 11
L
L
GND
12 −
NPN
GND
12 −
PNP
E53-Q4R4
E53-Q4Q4
E53-Q4HR4
E53-Q4HQ4H
+
11
V
L
12 −
0 to 10 V
E53-V44R4
+
11
mA
L
12 −
4 to 20mA
E53-C4R4
E53-C4DR4
Digital Controller E5CK
I-71