Z4W-V25R Datasheet, PDF (8/13 Pages) Omron Electronics LLC – Low-cost Displacement Sensor with 10-micron Resolution with Red LED
Z4W-V
Adjustment and Operation of the Linear Sensor Controller
Control panel of the Linear Sensor Controller
The control panel consists of two switches (MODE and MONI-
TOR), two adjusters (CENTER and WIDTH) and four indicators
(POWER, PASS, NG, INHIBIT) for monitoring.
By adjusting the settings of the Linear Sensor Controller and
compensating for the position of the LED Displacement Sensor,
the size of the object of standard dimensions is registered with
the Linear Sensor Controller. With the object of standard dimen-
sions, operate the LED Displacement Sensor as follows:
1. Set the MODE switch to NORMAL.
2. Turn the WIDTH adjuster counterclockwise to the MIN posi-
tion.
3. Turn the CENTER adjuster clockwise or counterclockwise
and set the adjuster to the position where the PASS indica-
tor is lit. If the PASS indicator is lit for a wide range of posi-
tions, set the adjuster in the middle of the range. If the
PASS indicator does not light with the CENTER adjuster in
any position, turn the WIDTH adjuster clockwise slightly.
An object of threshold dimensions or a multimeter can be used to
determine the tolerance (use the object where possible).
Determining Settings Using an Object
1. Prepare an object of threshold dimensions (an object with
the allowable upper threshold dimensions or with the allow-
able lower threshold dimensions) to be detected by the LED
Displacement Sensor.
2. Set the MODE switch to NORMAL.
3. Turn the WIDTH adjuster counterclockwise to the MIN posi-
tion. The NG indicator will light.
4. Turn the WIDTH adjuster clockwise slowly to the position
where the NG indicator turns OFF. The PASS indicator will
light.
Determining Settings Using a Multimeter
Determine the absolute tolerance, A (in mm), and obtain the volt-
age Vx (V) as follows (example for tolerance of ±0.5 mm):
1. Set the MONITOR switch to WIDTH.
2. Check the voltage of monitor terminals 10 (positive voltage
output) and 8 (negative voltage output) of the Linear Sensor
Controller with the multimeter in the 10-VDC or 5-VDC
range.
3. Turn the WIDTH adjuster clockwise or counterclockwise to
the position where the voltage reaches Vx (obtained from
the above formula).
Set the MODE switch to TRIG as follows:
1. Set the MODE switch to TRIG.
2. Set the MONITOR switch to INPUT or OFFSET (RUN).
3. Turn off the power and wire the output terminals (No. 4, 5,
and 6).
8
Z4W-V