Safety Precautions
Refer to Safety Precautions for All Solid State Relays.
■ Precautions for Correct Use
Please observe the following precautions to prevent failure to
operate, malfunction, or undesirable effect on product performance.
Connection
The SSR for DC switching use can connect to a load regardless of
the polarity of the positive and negative output terminals.
Close Mounting of Multiple Relays
If multiple Relays are mounted side by side, be aware that the outer
wall of each SSR works as a heat sink.
The SSR casing serves to dissipate heat. Install the Relays so that
they are adequately ventilated. If poor ventilation is unavoidable,
reduce the load current by half.
Protective Terminal
When using for AC inductive loads, connect the load terminals of the
SSR to an inrush absorber (varistor).
EMC Directive Compliance
1. AC-switching models comply with EMC Directives under the
following conditions ("-VD" models only).
Less than 3 m
Input G3F-VD Output
Load
Varistor: 470 V, 0.6 W
Varistor
Film capacitor: 1 µF, 250 VAC
Film Capacitor
• Connect a varistor between the output terminals.
• Connect a film capacitor to the load power supply.
• The input cable must be less than 3 m.
2. DC-switching models comply with EMC Directives under the
following conditions ("-VD" models only).
Less than 10 m
Input G3FD-VD Output
Load
• The input cable must be less than 10 m.
G3F/G3FD
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.