■ Ratings (at an Ambient Temperature of 25°C)
Input
Model
Rated voltage
G3F-203SN-VD
G3F-202SN-VD
G3F-203SLN-VD
G3FD-X03SN-VD
G3FD-102SN-VD
G3F-203S-VD
G3F-203SL-VD
G3FD-X03S-VD
G3FD-102S-VD
5 to 24 VDC
100/110 VAC
200/220 VAC
5 VDC
12 VDC
24 VDC
5 to 24 VDC
5 to 24 VDC
100/110 VAC
200/220 VAC
4 to 24 VDC
5 VDC
12 VDC
24 VDC
4 to 24 VDC
Operating voltage
4 to 28 VDC
75 to 125 VAC
150 to 250 VAC
4 to 6 VDC
9.6 to 14.4 VDC
19.2 to 28.8 VDC
4 to 28 VDC
4 to 28 VDC
75 to 125 VAC
150 to 250 VAC
3 to 28 VDC
4 to 6 VDC
9.6 to 14.4 VDC
19.2 to 28.8 VDC
3 to 28 VDC
Impedance
Voltage level
Must operate voltage Must release voltage
15 mA max. (See note.) 4 VDC max.
1 VDC min.
41 kΩ±20%
75 VAC max.
20 VAC min.
72 kΩ±20%
150 VAC max.
40 VAC min.
390 Ω±20%
4 VDC max.
1 VDC min.
900 Ω±20%
9.6 VDC max.
2 kΩ±20%
19.2 VDC max.
1.5 kΩ+20%/–10%
4 VDC max.
1.5 kΩ+20%/–10%
4 VDC max.
41 kΩ±20%
75 VAC max.
20 VAC min.
72 kΩ±20%
150 VAC max.
40 VAC min.
15 mA max. (See note.) 3 VDC max.
1 VDC min.
390 Ω±20%
4 VDC max.
900 Ω±20%
9.6 VDC max.
2 kΩ±20%
19.2 VDC max.
1.5 kΩ+20%/–10%
3 VDC max.
Note: 1. The input impedance is given for the maximum operating range. For details, refer to the Technical Guide for Solid State Relays.
2. Constant-current input circuit.
Output
Model
G3F-203SN-VD
G3F-203SLN-VD
G3F-203S-VD
G3F-203SL-VD
G3F-203SN-VD
G3FD-X03SN-VD
G3FD-X03S-VD
G3FD-102SN-VD
G3FD-102S-VD
Rated load
voltage
100 to 240 VAC
100 to 240 VAC
4 to 48 VDC
5 to 110 VDC
Load voltage range
75 to 264 VAC
75 to 264 VAC
3 to 52.8 VDC
3 to 125 VDC
Applicable load
Load current
0.1 to 3 A at 40°C
0.1 to 2 A at 40°C
0.1 to 3 A at 40°C
0.1 to 2 A at 40°C
Inrush current
45 A (60 Hz, 1 cycle)
45 A (60 Hz, 1 cycle)
18 A (10 ms)
10 A (10 ms)