S8VK-G Datasheet, PDF (4/22 Pages) Omron Electronics LLC – Reliable and Easy Operation Resistant in tough environments Easy and fast installation The most compact size on the market
S8VK-G
Power ratings
60 W
120 W
Item
Output voltage
12 V
24 V
24 V
Efficiency (Typical)
230 VAC input
85%
88%
89%
Voltage *1
100 to 240 VAC, 90 to 350 VDC (allowable range: 85 to 264 VAC) *6
Frequency *1
50/60 Hz (47 to 450 Hz)
50/60 Hz (47 to 63 Hz)
115 VAC input
Current (Typical)
230 VAC input
1.0 A
0.6 A
1.1 A
0.7 A
1.3 A
Input
Power factor
(Typical)
230 VAC input
0.46
0.45
0.94
Harmonic current emissions
Conforms to EN61000-3-2
Leakage current 115 VAC input
(Typical)
230 VAC input
0.16 mA
0.30 mA
0.24 mA
0.38 mA
Inrush current
(Typical) *2
115 VAC input
230 VAC input
16 A
32 A
Voltage adjustment range *3
–10% to 15% (with V.ADJ) (guaranteed)
Ripple *4
at 20 MHz (Typical) 150 mV
50 mV
150 mV
Input variation influence
0.5% max. (at 85 to 264 VAC input, 100% load)
Output
Load variation Influence
(Rated Input voltage)
Temperature variation influence
2.0% max. (12 V), 1.5% max. (24 V), at 0% to 100% load
0.05%/°C max.
Start up time
(Typical) *2
115 VAC input
230 VAC input
570 ms
430 ms
650 ms
500 ms
790 ms
750 ms
Hold time
(Typical) *2
115 VAC input
230 VAC input
26 ms
139 ms
25 ms
129 ms
42 ms
42 ms
Overload protection *2
121% to 160% of rated load current, (130% typ value)
121% to160% of rated load current,
(125% typ value)
Additional Overvoltage protection *2
functions Power Boost
Yes *5
120% of rated current (Refer to Engineering Data)
Parallel operation
Yes (Refer to Engineering Data)
Series operation
Possible for up to two Power Supplies (with external diode)
Ambient operating temperature
–40 to 70°C (Refer to Engineering Data)
Storage temperature
–40 to 85°C
Ambient operating humidity
0% to 95% (Storage humidity: 0% to 95%)
Dielectric strength
(detection current: 20 mA)
3.0 kVAC for 1 min. (between all inputs and outputs)
2.0 kVAC for 1 min. (between all inputs and PE terminal)
1.0 kVAC for 1 min. (between all outputs and PE terminal)
Insulation resistance
100 M min. (between all outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
10 to 150 Hz, 0.35-mm single amplitude (5 G max.) for 80 min. each in X, Y, and Z directions
Shock resistance
150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Output indicatior
Yes (color: green), lighting from 80% to 90% or more of rated voltage
Others
EMI
Conducted Emission Conforms to EN61204-3 EN55011 Class B and based on FCC Class A
Radiated Emission Conforms to EN61204-3 EN55011 Class B
EMS
Conforms to EN61204-3 high severity levels
Approved Standards
UL Listed: UL508 (Listing, For 60 W only Class2 Output: Per UL1310)
UL UR: UL60950-1 (Recognition)
cUL: CSA C22.2 No.107.1 (For 60 W only Class2 Output: Per CSA C22.2 No.223)
cUR: CSA C22.2 No.60950-1
EN/VDE: EN50178 (=VDE0160), EN60950-1 (=VDE0805)
Lloyd’s standards *7
Fulfilled Standards
SELV (EN60950-1/EN50178/UL60950-1), PELV(EN60204-1, EN50178),
Safety of Power Transformers (EN61558-2-16)
EN50274 for Terminal parts
Degree of protection
IP20 by EN / IEC60529
SEMI
F47-0706 (200 to 240 VAC)
Weight
260 g
620 g
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*2. For a cold start at 25C. Refer to Engineering Data on page 11 for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting
the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
*4. A characteristic when the ambient operating temperature is between –25 to 70C.
*5. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*6. 90 to 350 VDC’s UL standards are scheduled to obtain certification in June, 2013.
*7. Scheduled to obtain certification in June, 2013.