English
Language : 

S8VK-G Datasheet, PDF (18/22 Pages) Omron Electronics LLC – Reliable and Easy Operation Resistant in tough environments Easy and fast installation The most compact size on the market
S8VK-G
Precautions for Safe Use
Wiring
 Connect the ground completely. A protective earthing terminal
stipulated in safety standardsis used. Electric shock or malfunction
may occur if the ground is not connected completely.
 Minor fire may possibly occur. Ensure that input and output
terminals are wired correctly.
 Do not apply more than 75-N force to the terminal block when
tightening it.
 Be sure to remove the sheet covering the Product for machining
before power-ON so that it does not interfere with heat dissipation.
 Use the following material for the wires to be connected to the
S8VK-G to prevent smoking or ignition caused by abnormal loads.
Terminals and Wiring
Model
American
Wire Gauge
INPUT
Solid Wire
/Stranded Wire
S8VK-G01505
S8VK-G01512 AWG24 to 12
0.25 to 4 mm2
/0.25 to 2.5 mm2
S8VK-G01524
S8VK-G03005
S8VK-G03012
S8VK-G03024
AWG24 to 12
0.25 to 4 mm2
/0.25 to 2.5 mm2
S8VK-G06012
S8VK-G06024
S8VK-G12024
S8VK-G24024
S8VK-G24048
AWG22 to 12
AWG22 to 10
AWG20 to 10
0.35 to 4 mm2
/0.35 to 2.5 mm2
0.35 to 6 mm2
/0.35 to 4 mm2
0.5 to 6 mm2
/0.5 to 4 mm2
S8VK-G48024
S8VK-G48048
AWG16 to 10
1.5 to 6 mm2
/1.5 to 4 mm2
OUTPUT
American
Wire Gauge
Solid Wire
/Stranded Wire
AWG20 to 12
0.5 to 4 mm2
/0.5 to 2.5 mm2
AWG22 to 12
0.35 to 4 mm2
/0.35 to 2.5 mm2
AWG24 to 12
0.25 to 4 mm2
/0.25 to 2.5 mm2
AWG18 to 12
0.75 to 4 mm2
/0.75 to 2.5 mm2
AWG20 to 12
0.5 to 4 mm2
/0.5 to 2.5 mm2
AWG22 to 12
0.35 to 4 mm2
/0.35 to 2.5 mm2
AWG18 to 12
0.75 to 4 mm2
/0.75 to 2.5 mm2
AWG20 to 12
0.5 to 4 mm2
/0.5 to 2.5 mm2
AWG18 to 10
0.75 to 6 mm2
/0.75 to 4 mm2
AWG14 to 10
2.5 to 6 mm2
/2.5 to 4 mm2
AWG18 to 10
0.75 to 6 mm2
/0.75 to 4 mm2
AWG12 to 10
4 to 6 mm2
/4 mm2
AWG14 to 10
2.5 to 6 mm2
/2.5 to 4 mm2
American
Wire Gauge
PE
Solid Wire
/Stranded Wire
AWG14 or thicker
2.5 mm2 or thicker
/2.5 mm2 or thicker
 Strip I/O wires for 8 mm when using a screwless terminal block.
Note: The rated current for output terminals is 10 A per terminal.
Be sure to use multiple terminals simultaneously for current that exceeds the terminal rating.
When applying a current of 10 A or more, use at least two terminals each for the positive and negative wires.
Installation Environment
 Do not use the Power Supply in locations subject to shocks or
vibrations. In particular, install the Power Supply as far away as
possible from contactors or other devices that are a vibration
source.
 Install the Power Supply well away from any sources of strong,
high-frequency noise and surge.
Operating Life
 The life of a Power Supply is determined by the life of the
electrolytic capacitors used inside. Here, Arrhenius Law applies,
i.e., the life will be cut in half for each rise of 10C or the life will be
doubled for each drop of 10C. The life of the Power Supply can
thus be increased by reducing its internal temperature.
Ambient Operating and Storage Environments
 Store the Power Supply at a temperature of 40 to 85C and a
humidity of 0% to 95%.
 Do not use the Power Supply in areas outside the derating curve
otherwise, internal parts may occasionally deteriorate or be
damaged.
 Use the Power Supply at a humidity of 0% to 95%.
 Do not use the Power Supply in locations subject to direct sunlight.
 Do not use locations where liquids, foreign matter, or corrosive
gases may enter the interior of Products.
18