PYF14S Datasheet, PDF (4/6 Pages) Omron Electronics LLC – Screwless Clamp Terminal Socket
PYFjjS
J APPLICABLE WIRES
Applicable Wire Sizes
0.2 to 1.5 mm2, AWG24 to AWG16
Applicable Wire Type
Solid wires, stranded wires, flexible wires, or wires with ferules
can be used.
(See note 1) < 2.2 Diameter D (mm) 3.2 (3.5: see note 2))
Conductor diameter d (mm) or length of sides a and b (mm)
1.9
Wires with Ferules
PYFjjS
Note: 1. If the overall diameter of the wire is less than 2.2 mm,
do not insert the wire past the conductor. Refer to the
following diagrams.
2. If the overall diameter of the wire is over 3.2 mm, it will be
difficult to use double wiring.
Examples of Applicable Wires (Confirmed Using Catalog Information)
Type of wire
Equipment wire 2491X
BS6004
Switchgear BS6231
Switchgear BS6231
Tri-rated control and switchgear
Conduit
UL1007
UL1015
UL1061
UL1430
Conductor type
Flexible
Solid
Solid
Flexible
Flexible
Stranded
Flexible
Flexible
Flexible
Flexible
See note 1, above.
0.5 mm2
18AWG
18AWG
18AWG
Recommended wire
sizes
0.5, 0.75, 1.0 mm2
1.0 mm2
0.5, 0.75 mm2
0.5, 0.75, 1.0, 1.5 mm2
1.5 mm2
16AWG
18AWG, 16AWG
16AWG
See note 2, above.
1.5 mm2
1.5 mm2
1.0 mm2
J WIRING
Use wires of the applicable sizes specified above. The length of
the exposed conductor should be 8 to 9 mm.
8 to 9 mm
Fig. 1 Exposed Conductor Length
Use the following wiring procedure.
1. Insert the specified screwdriver into the release hole located
beside the wire connection hole where the wire is to be
inserted.
2. Insert the exposed conductor into the wire connection hole.
Insert
Wire connection holes
Release holes
3. Pull out the screwdriver.
Fig. 2 Wire Connection Holes and Release Holes
Wire connection hole
Release hole
Fig. 3 Section A-A of Fig. 2
4
Screwdriver
Insert
Pull out