S8TS Datasheet, PDF (3/3 Pages) Omron Electronics LLC – Switch Mode Power Supply
5-V Models (Basic Block: S8TS-02505@)
Item
Efficiency (typical)
Input
Voltage
Frequency
Current
100 V input
200 V input
Power factor
Leakage current
100 V input
240 V input
Inrush current
(25°C, cold start)
(See note 2.)
100 V input
200 V input
Output (See Voltage adjustment range
note 2.)
Ripple
Input variation influence
Temperature variation influence
Load variation influence
Startup time (See note 3.)
Hold time (See note 3.)
Additional
functions
Overcurrent protection (See note 3.)
Overvoltage protection (See note 3.)
Parallel operation
N+1 redundant system
Series operation
Undervoltage indicator (See note 3.)
Undervoltage detection output (See note
3.)
Other
Ambient operating temperature (See note
3.)
Ambient humidity
Dielectric strength
Insulation resistance
Vibration resistance
Shock resistance
Output indicator
Electromagnetic interference
EMI
Power factor correction
EMS
Approved standards
Weight
62% min. (with rated input, 100% load)
100 to 240 VAC (85 to 264 VAC)
50/60 Hz (47 to 63 Hz)
0.7 A max.
0.4 A max.
0.8 min. (with rated input, 100% load)
0.35 mA max.
0.7 mA max.
25 A max.
50 A max.
Single operation
5 V ± 10% (with V. ADJ) (See note 1.)
2% (p-p) max.
0.5% max. (with 85 to 264 VAC input, 100% load)
0.05%/°C max. (with rated input and output)
1.5% max. (with rated input, 10% to 100% load)
1,000 ms max.
20 ms min. (with 100/200 VAC, rated input)
105% to 125% of rated load current, inverted L drop type, automatic reset
Yes
No
No
Yes (with the external diode)
Yes (color: red)
Yes (open collector output), 30 VDC max., 50 mA max.
Operating: Refer to the derating curve in Engineering Data.
Storage: −25 to 65°C (with no icing or condensation)
Operating: 25% to 85%, Storage: 25% to 90%
3.0 kVAC, 50/60 Hz for 1 minute (between all inputs and all outputs; detection current: 20 mA)
2.0 kVAC, 50/60 Hz for 1 minute (between all inputs and GR terminal; detection current: 20 mA)
1.0 kVAC for 1 minute (between all outputs and GR terminal; detection current: 20 mA)
100 MΩ min. (between all outputs and all inputs, and between all outputs and GR terminal) at 500 VDC
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Yes (color: green)
Conforms to FCC Class A, EN50081-1
Conforms to EN50081-1/1992
Conforms to EN61000-3-2, EN61000-3-2A14
Conforms to EN61000-6-2/1999
UL:
cUL:
EN/VDE:
508 (Listing), 1950, 1604 (Class I, Division 2, Groups A, B, C, D
Hazardous Locations)
CSA C22.2 No.14, No.213 (Class I, Division 2, Groups A, B, C, D
Hazardous Locations), No. 950
EN50178 (=VDE0160), 60950 (=VDE0806)
450 g max.
Note 1. If set to less than −10%, the undervoltage detection function may operate. Ensure that the output capacity and output current after adjust-
ment do not exceed the rated output capacity and rated output current respectively.
2. The output current is specified at power output terminals.
3. Refer to the explanations of functions on page B-56 for details.
4. Be sure to mount End Plates (PFP-M) on both ends of the Power Supply.
■ Reference Value
Item
Reliability (MTBF)
Life expectancy
Value
250,000 hrs min.
10 yrs min.
Definition
MTBF stands for Mean Time Between Failures, which is calculated according to the probability of acci-
dental device failures, and indicates reliability of devices. Therefore, it does not necessarily represent the
life of the product.
The life expectancy indicates average operating hours under the ambient temperature of 40°C and a load
rate of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic ca-
pacitor.
Switch Mode Power Supply S8TS