S8TS Datasheet, PDF (2/3 Pages) Omron Electronics LLC – Switch Mode Power Supply
Specifications
■ Ratings/Characteristics
24/12-V Models (Basic Block: S8TS-06024@/S8TS-03012@)
Efficiency
Input
Output (See
note 3.)
Additional
functions
Other
Item
Voltage
Frequency
Current
100 V input
200 V input
Power factor
Leakage current
100 V input
240 V input
Inrush current
(25°C, cold start)
(See note 4.)
100 V input
200 V input
Voltage adjustment range
Ripple
Input variation influence
Load variation influence
Temperature variation influence
Startup time (See note 4.)
Hold time (See note 4.)
Overcurrent protection (See note 4.)
Overvoltage protection (See note 4.)
Parallel operation
N+1 redundant system
Series operation
Undervoltage indicator (See note 4.)
Undervoltage detection output (See
note 4.)
Ambient operating temperature (See
note 4.)
Ambient humidity
Dielectric strength
Insulation resistance
Vibration resistance
Shock resistance
Output indicator
Electromagnetic interference
EMI
Power factor correction
EMS
Approved standards
Weight
Single operation
Parallel operation
24-V models: 75% min.; 12-V models: 70% min. (with rated input, 100% load)
100 to 240 VAC (85 to 264 VAC)
50/60 Hz (47 to 63 Hz)
24-V models: 1.0 A max.
12-V models: 0.7 A max.
24-V models: 1.0 A × (No. of Blocks) max.
12-V models: 0.7 A × (No. of Blocks) max.
24-V models: 0.5 A max.
12-V models: 0.4 A max.
24-V models: 0.5 A × (No. of Blocks) max.
12-V models: 0.4 A × (No. of Blocks) max.
24-V models: 0.9 min.; 12-V models: 0.8 min. (with rated input, 100% load) (See note 3.)
0.35 mA max.
0.35 mA × (No. of Blocks) max.
0.7 mA max.
0.7 mA × (No. of Blocks) max.
25 A max.
25 A × (No. of Blocks) max.
50 A max.
50 A × (No. of Blocks) max.
24-V models: 22 to 28 V
12-V models: 12 V ±10% (with V.ADJ) (See note 1.)
2% (p-p) max.
0.5% max. (with 85 to 264 VAC input, 100% load)
2% max. (with rated input, 10% to 100% load)
3% max. (with rated input, 10% to 100% load)
0.05%/°C max. (with rated input and output)
1,000 ms max.
20 ms min. (with 100/200 VAC, rated input)
105% to 125% of rated load current, inverted L drop 100% to 125% of rated load current inverted L drop
type, automatic reset
type, automatic reset
Yes
Yes, 4 Blocks max.
Yes, 5 Blocks max.
Yes
Yes (color: red)
Yes (open collector output), 30 VDC max., 50 mA max.
Operating: Refer to the derating curve in Engineering Data.
Storage: −25 to 65°C (with no icing or condensation)
Operating: 25% to 85%; Storage: 25% to 90%
3.0 kVAC, 50/60 Hz for 1 minute (between all inputs and all outputs; detection current: 20 mA)
2.0 kVAC, 50/60 Hz for 1 minute (between all inputs and GR terminal; detection current: 20 mA)
1.0 kVAC for 1 minute (between all outputs and GR terminal; detection current: 20 mA)
100 MΩ min. (between all outputs and all inputs, and between all outputs and GR terminal) at 500 VDC
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
150 m/s2, 3 times each in ±X, ±Y, and ±Z directions
Yes (color: green)
Conforms to FCC Class A, EN50081-1
Conforms to EN50081-1/1992
Conforms to EN61000-3-2, EN61000-3-2 A14
Conforms to EN61000-6-2/1999
UL:
cUL:
EN/VDE:
508 (Listing; Class 2: Per UL1310), 1950, 1604 (Class I, Division 2, Groups A, B, C, D
Hazardous Locations))
CSA C22.2 No.14, No.213 (Class I, Division 2, Groups A, B, C, D
Hazardous Locations), No. 950 (Class 2) (See note 2.)
EN50178 (=VDE0160), 60950 (=VDE0806)
450 g max.
450 g × (No. of Blocks) max.
Note 1. Refer to page B-59 for details on adjusting the output voltage for parallel operation. If set to less than −10%, the undervoltage detection
function may operate. Ensure that the output capacity and output current after adjustment do not exceed the rated output capacity and
rated output current respectively.
2. Class 2 approval does not apply to parallel operation.
3. The output current is specified at power output terminals.
4. Refer to the explanations of functions on page B-56 for details.
5. Be sure to mount End Plates (PFP-M) on both ends of the Power Supply.
B-54
Switch Mode Power Supply S8TS