English
Language : 

G3NA-210B-DC5-24 Datasheet, PDF (11/18 Pages) Omron Electronics LLC – New Models with 75-A and 90-A Output Join the Previous Models with 5- to 50-A Output.
■ Approvals
UL Recognized (File No. E64562) / CSA Certified (File No. LR35535) - - Ambient Temp. = 40°C
SSR type
G3NA-205B
G3NA-210B
G3NA-220B
G3NA-225B
G3NA-240B
G3NA-410B
G3NA-420B
G3NA-425B
G3NA-440B
G3NA-450B
G3NA-D210B
Input voltage
Load type
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 240 VAC
General use/Tungsten
Motor
General use/Tungsten
Motor
General use/Tungsten
Motor
General use/Tungsten
Motor
General use/Tungsten
Motor
General use/Tungsten
Motor
General use/Tungsten
Motor
General use/Tungsten
Motor
General use/Tungsten
Motor
General use/Tungsten
Motor
General use
Contact ratings
Without heat sink
With heat sink (see note 1)
3 A, 240 VAC
5 A, 240 VAC
2.5 FLA, 15 LRA, 240 VAC
2.5 FLA, 15 LRA, 240 VAC
4 A, 240 VAC
10 A, 240 VAC
2.5 FLA, 15 LRA, 240 VAC
5 FLA, 30 LRA, 240 VAC
4 A, 240 VAC
20 A, 240 VAC
2.5 FLA, 15 LRA, 240 VAC
10 FLA, 60 LRA, 240 VAC
4 A, 240 VAC
25 A, 240 VAC
2.5 FLA, 15 LRA, 240 VAC
12 FLA, 72 LRA, 240 VAC
6 A, 240 VAC
40 A, 240 VAC
5 FLA, 30 LRA, 240 VAC
20 FLA, 120 LRA, 240 VAC
4 A, 480 VAC
10 A, 480 VAC
2.5 FLA, 15 LRA, 480 VAC
5 FLA, 30 LRA, 480 VAC
4 A, 480 VAC
20 A, 480 VAC
2.5 FLA, 15 LRA, 480 VAC
10 FLA, 60 LRA, 480 VAC
4 A, 480 VAC
25 A, 480 VAC
2.5 FLA, 15 LRA, 480 VAC
12 FLA, 72 LRA, 480 VAC
6 A, 480 VAC
40 A, 480 VAC
5 FLA, 30 LRA, 480 VAC
20 FLA, 120 LRA, 480 VAC
6 A, 480 VAC
50 A, 480 VAC
5 FLA, 30 LRA, 480 VAC
24 FLA, 144 LRA, 480 VAC
4 A, 200 VDC
10 A, 200 VDC
Note: 1. When used with the proper OMRON heat sink part number or an appropriately dimensioned equivalent.
2. The rated values approved by each of the safety standards (e.g., UL, CSA, and TÜV) may be different from the performance
characteristics individually defined in this catalog.
3. In the interest of product improvement, specifications are subject to change.