■ Mounting
Standard Mounting
(DIN Rail Mounting Bracket Models)
Correct
Standard Mounting
(Bottom Mounting Models)
Correct
*1
Horizontal Mounting
Correct
*1
Face-up Mounting
Face-up Mounting
(DIN Rail Mounting Bracket Models)
Incorrect
Correct
*1
Face-down Mounting
Face-down Mounting
(DIN Rail Mounting Bracket Models)
Incorrect
Incorrect
S8VM
■ Remote Sensing Function
(S8VM-100@@@@/150@@@@ only)
This function compensates a voltage drop on the load lines.
To use this function, connect after removing the two short bars of the
remote sensing terminal.
Short bar
V.ADJ
*1
DC ON
+S
+V
−V
−S
*2
Note: 1. Use a 2-conductor shielded cable as a connection wire (*1).
2. Use as thick a wire as possible since high voltage drops on
the load lines (*2) may activate the overvoltage protection
function.
3. Use when the voltage drop is 0.3 V or lower.
4. When the +S and −S terminals are opened with the short
bar removed, the overvoltage protection function is activat-
ed and the output voltage will be cut off.
5. If the load line is too long, use an electrolytic capacitor in the
following 3 locations:
1) Across the load terminals
2) Between the +S terminal and + terminal
3) Between the −S terminal and − terminal
Select the capacity of the connected capacitor from be-
tween several tens to several hundreds of µF as a guide,
and then determine the capacity when actually connecting
the capacitor between terminals as shown below.
+
V.ADJ
DC ON
+S
+
+V
−V
+
−S
■ Inrush Current, Startup Time,
Output Hold Time
Input ON
AC input
voltage
Input OFF
Surface Mounting for
Surface Mounting for Face-up
Standard Mounting Direction Mounting
Correct
Correct
Terminal block
The terminals are in front. The terminals are on the top.
Note: 1. Improper mounting will interfere with heat dissipation and
may occasionally result in deterioration or damage of inter-
nal parts.
Use the Power Supply within the derating curve for the
mounting direction that is used.
2. Use the metal plate as the mounting panel (*1).
3. Install the Power Supply so that the air flow circulates
around the Power Supply, as the Power Supply is designed
to radiate heat by means of natural air flow.
4. Mounting screw tightening torque
(recommended value: M3 (0.49 N·m))
AC input
current
Inrush current on input application
90%
95%
Output
voltage
Startup time
Hold time
■ Reference Values
Item
Value
Definition
Reliability
(MTBF)
135,000 hrs MTBF stands for Mean Time Between Failures, which
min.
is calculated according to the probability of accidental
device failures, and indicates the reliability of a device.
Therefore, it does not necessarily represent the life of
the Power Supply.
Life expectancy 10 yrs. min. The life expectancy indicates average operating hours
under the ambient temperature of 40°C and a load
rate of 50%.
Normally this is determined by the life expectancy of
the built-in aluminum electrolytic capacitor.
10