D1U54-D-1200-12-HX4PC Datasheet, PDF (5/6 Pages) Murata Power Solutions Inc. – 54mm 1U Front End DC-DC Power Converter
D1U54-D-1200-12-Hx4PC Series
54mm 1U Front End DC-DC Power Converter
WIRING DIAGRAM FOR OUTPUT
Dotted lines show optional remote sense connections.
Optional remote sense lines can be attached to a load that is a distance
away from the power supply to improve regulation at the load.
V1_SENSE (Main Output Remote Sense)
V1_SENSE (Main Output Remote Sense)
E3
+12V main output
6-10
D1U54P
12V load
1-5 +12V main output return
D3
B5 (or D4)
V1_SENSE_R
ISHARE
+12V main output 6-10 E3
D1U54P
+12V main output return 1-5
V1_SENSE_R D3
ISHARE B5 (or D4)
A1,B1,C1,D1,E1
B4
A2,B2
VSB
PS_ON
VSB_return
VSB load
FET, BJT, wire
or switch (debounced )
to turn on +12V main output
VSB A1,B1,C1,D1,E1
PS_ON B4
VSB_return A2,B2
A5 (or A3) PS_KILL
PS_KILL A5 (or A3)
CURRENT SHARING NOTES
1. Main 12VDC Output: Analogue active share bus. The ISHARE bus (Pin B5 or D4) must be connected on all sharing modules. It is not required that the SENSE signals are con-
nected to the remote load for current share to operate correctly.
2. Up to eight (8) power modules can be connected in parallel (non-redundant) or N+1 configuration. The current share bus is analogue bi-directional (can source or sink current
from the ISHARE bus).
The voltage of the bus would measure 8VDC for a single power module at 100% load; for two (2) modules sharing a common load the ISHARE bus voltage would be 4V for a
perfect 50/50 current share scenario.
3. The VSB (Standby Output) output of the power module can also be connected in parallel; internal output isolation devices are provided however the combined available power is
limited to that available from a single power module (3.3V or 5V; 20W) irrespective of the number of modules connected in parallel.
www.murata-ps.com/support
D1U54-D-1200-12-Hx4PC.A01 Page 5 of 6