English
Language : 

D1U54-D-1200-12-HX4PC Datasheet, PDF (1/6 Pages) Murata Power Solutions Inc. – 54mm 1U Front End DC-DC Power Converter
www.murata-ps.com
D1U54-D-1200-12-Hx4PC Series
54mm 1U Front End DC-DC Power Converter
FEATURES
1200W output power (no derating across the
full DC input voltage range)
1.57"(1U) x 12.65" x 2.15"
92% efficiency
12VDC Main output
3.3VSB or 5VSB output (20W)
>28W/in3 power density
N+1 Redundancy Capable; hot plug/swap (up to
8 modules in parallel)
Active current sharing on 12V main output;
integral MOSFET ORING
Over-Voltage, Over-Current; Over-Temperature
Protection
Internal variable speed cooling fans
PMBus™ Power Management Bus
RoHS Compliant
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
Available now at
www.murata-ps.com/en/3d/acdc.html
PRODUCT OVERVIEW
The D1U54-D-1200-12-Hx4PC series are highly efficient 1200 watt, DC input front end modules with a 12V main output
and a choice of 3.3V or 5V (20W) standby rails. The power module is able to current share with up to eight (8) other power
modules of the same type operating in parallel or N+1 redundancy. The supplies may be hot plugged, and include integral
isolation devices.
The power modules are fully protected from overload and overvoltage and are able to auto-recover from overtemperature
faults. A Status LED is provided on the front panel and additional control and status reporting is provided by hardware
logic signals and via a PMBus™ digital interface.
A low profile sub 1U height enclosure provides an excellent power density of >28W/in3 that is ideal for delivering reliable,
efficient power to servers; workstations; storage systems and other 12V distributed power systems, including direct
operation from intermediate bus converters.
ORDERING GUIDE
Part Number
D1U54-D-1200-12-HC4PC
D1U54-D-1200-12-HA4PC
D1U54-D-1200-12-HC3PC
D1U54-D-1200-12-HA3PC
Power Output
1200W
Main Output
12V
Standby Output
3.3V
5V
3.3V
5V
Airflow
Back to Front
Front to Back
INPUT CHARACTERISTICS
Parameter
DC Input Voltage Operating Range
Turn-on Input Voltage
Turn-off Input Voltage
Maximum Current @ VIN = -48Vdc
DC Input Inrush Peak Current
Efficiency (-48Vdc)
Reverse polarity protection
Conditions
Min Typ Max Units
-40 -48/-60 -72
Ramp Up
-39.5 -40 -40.5 Vdc
Ramp Down
-35.5 -36 -36.5
1200W
40
Adc
Cold start between 0 to
-40
200ms
-72
50
100
Apk
20% FL
90
50% FL
92
%
100% FL
90
Reversed input cables; no
internal/external fuse failure
+40
+72 Vdc
OUTPUT VOLTAGE CHARATERISTICS
Output Voltage Parameter
Voltage Set Point
Main
Line & Load Regulation
Ripple & Noise1
12V
Output Current
Load Capacitance
Voltage Set Point
Line & Load Regulation
3.3VSB
Ripple Voltage & Noise1
Output Current
Load Capacitance
Voltage Set Point
Line & Load Regulation
5VSB
Ripple Voltage & Noise1
Output Current
Load Capacitance
Conditions
Combined regulation
20MHz Bandwidth
-40Vdc to -72Vdc DC input
Combined regulation
20MHz Bandwidth
20MHz Bandwidth
Min. Typical Max. Units
11.6
12
12.4
Vdc
120 mV P-P
0
100A
A
30,000 μF
3.14
3.3
3.46
Vdc
120 mV P-P
0
6
A
10,000 μF
4.76
5.0
5.24
Vdc
120 mV P-P
0
4
A
10,000 μF
1 Ripple and noise are measurements are to be performed with a parallel combination of a 0.1μF ceramic capacitor
and 10μF tantalum capacitance on each of the power module output measurement nodes. A short coaxial cable from
measurement point to ’scope shall be used
Ḥ
For full details go to
www.murata-ps.com/rohs
CB
Test Certificate
and Test Report
PM
www.murata-ps.com/support
D1U54-D-1200-12-Hx4PC.A01 Page 1 of 6