English
Language : 

MVAC400-12AFR Datasheet, PDF (1/8 Pages) Murata Power Solutions Inc. – 400W 3 x 5 High Density AC-DC Power Supply Converter
www.murata-ps.com
FEATURES
IEC60601 Ed 3 medical (2 X MOPP Pri-Sec)
EN60950 ITE safety approved
400W compact high density
3" x 5" standard footprint
High efficiency up to 94%
Remote sense
Remote On/Off, Power OK
Universal AC input with active PFC
Less than 1U high – 1.4"
Convection cooled operation up to 250W
Isolated 12V@1A fan output
Isolated 5V@2A standby output
RoHS compliant
Active inrush protection
Current sharing option
DESCRIPTION
The MVAC400 series switching power supplies
utilize advanced component and circuit
technologies to deliver high efficiency. Designed
for medical, computing, communications, telecom
and other OEM applications to satisfy 1U height
design considerations, the MVAC400 Series
measures only 3.0" x 5.0" x 1.40". All models
offer universal AC input with active power factor
correction (PFC) and compliance to worldwide
safety and EMC standards.
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
www.murata-ps.com/en/3d/acdc.html
Available now at
www.murata-ps.com/en/3d/acdc.html
Ḥ
For full details go to
www.murata-ps.com/rohs
www.murata-ps.com/support
MVAC400 Series
400W 3" x 5" High Density AC-DC Power Supply Converter
ORDERING GUIDE
Model Number
Natural Convection Cooling
Forced Air Cooling
Main Output Fan Output Aux Output
(V1)
(V2)
(V3)
MVAC400-12AF
12V
MVAC400-24AF
24V
MVAC400-48AF
50V
MVAC400-12AFD
12V
MVAC400-24AFD
250W
400W @ 250LFM
24V
12V
5V
MVAC400-48AFD
50V
MVAC400-24AFT*
24V
MVAC400-12AFR*
12V
MVAC400-12AFT*
12V
MVAC-COVER
Optional cover kit assembly; see MVAC-COVER datasheet for details.
Refer to page 2 for current sharing details for MVAC400-xxAFD and MVAC400-xxAFR models.
* CCC Certification is not available for these models.
INPUT CHARACTERISTICS
Parameter
Input Voltage Operating Range
Input Frequency
Turn-on Input Voltage
Turn-off Input Voltage
Input Current
No Load Input Power7
Inrush Current
Power Factor
Conditions
Min. Typ. Max. Units
Single phase
90 115/230 264
Vac
DC
127
300
Vdc
47 50/60 63
Hz
Input rising
Input falling
80
90
Vac
70
80
90Vac input, full load all outputs
5.5
A
(PS_ON = OFF, 5V_Aux = 0A)
1.5
2.0
W
At 264Vac, at 25°C cold start
15
Apk
At 230Vac, full load
0.98
OUTPUT CHARACTERISTICS
Model Number
Main Output
Voltage (V1)
MVAC400-12AFx
12V
MVAC400-24AFx
24V
MVAC400-48AFx
50V
Load Current
0 to 33.3A
0 to 16.7A
0 to 8.0A
Maximum Load
Capacitance
0 to 2200µF
0 to 470µF
0 to 150µF
Line, Load, Cross
Regulation6
± 1%
± 1%
± 1%
Typical Efficiency
@230Vac
93%
93%
94%
MAIN OUTPUT CHARACTERISTICS (ALL MODELS)
Parameter
Conditions
Transient Response9
50% load step, 1A/µsec slew rate
Settling Time to 1% of Nominal
Turn On Delay
After application of input power
Output Voltage Rise
Monotonic5
Output Holdup
120Vac/60Hz, full load
Temperature Coefficient
Ripple Voltage & Noise1
Compensates for up to 0.5V of lead drop with
Remote Sense
remote sense connected. Protected against
short circuit and reverse connection.
Hot Swap Transients10
All outputs remain in regulation
Typ.
Max. Units
±5
%
500
µsec
3
sec
20
50
msec
0.02 %/°C
1
%
500
mV
± 10
%
AUXILIARY OUTPUT CHARACTERISTICS (ALL MODELS)
Auxiliary Output
Aux Output
Voltage8
Load Current Load Capacitance
Fan (V2)
12V
0 to 1A
0 to 220µF
Aux (V3)
5V
0 to 2A
0 to 220µF
Line, Load, Cross
Regulation3
± 10%
± 5%
Ripple Voltage &
Noise1
2%
1%
CB
Test Certificate
and Test Report
MVAC400.B02 Page 1 of 8