English
Language : 

GS200-6S Datasheet, PDF (3/4 Pages) MTU Onsite Energy Corporation – GAS GENERATOR SET
3 / //  / GS200-6S
APPLICATION DATA
//  Engine
Manufacturer
Model
Type
Arrangement
Displacement: L (in3)
Bore: cm (in)
Stroke: cm (in)
Compression Ratio
Rated RPM
Engine Governor
Maximum Power (NG): kWm (bhp)
Maximum Power (LP): kWm (bhp)
Speed Regulation
Air Cleaner
//  Liquid Capacity (Lubrication)
Total Oil System: L (gal)
Engine Jacket Water Capacity: L (gal)
System Coolant Capacity: L (gal)
//  Electrical
Electric Volts DC
Cold Cranking Amps Under -17.8 °C (0 °F)
//  Cooling - Radiator System
Doosan
11.1L CAC
4-Cycle
6-Inline
11.1 (673)
12.3 (4.84)
15.5 (6.1)
10.5:1
1,800
Bosch
225 (302)
155 (208)
±0.5%
Dry
Ambient Capacity of Radiator: °C (°F)
50 (122)*
Maximum Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: kPa (in. H20)
Water Pump Capacity: L/min (gpm)
0.12 (0.5)
310 (82)
Heat Rejection to Coolant: kW (BTUM) 194.6 (11,071)
Heat Radiated to Ambient: kW (BTUM) 40.4 (2,295)
Fan Power: kW (hp)
10.4 (13.9)
10.4 (13.9)
* Installation of enclosures reduces the ambient capacity
of the cooling system by 1 °C (1.8 °F). Gravity exhaust
louvers reduce ambient capacity of the cooling system
by an additional 3 °C (5.5 °F).
//  Air Requirements
28.5 (8)
25 (5.5)
149 (32.8)
Aspirating: *m3/min (SCFM)
Air Flow Required for Rad.
Cooled Unit: **m3/min (SCFM)
Remote Cooled Applications;
Air Flow Required for Dissipation
of Radiated Gen-set Heat for a
Max of 25 °F Rise: *m3/min (SCFM)
11.7 (400)
631 (22,300)
237 (8,365)
24
1,050
* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)
** At 0.25 kPa (1 in. H20) static pressure and
52 °C (125 °F) at radiator
//  Fuel Inlet
Fuel Supply Connection Size
Fuel Supply Pressure: mm H20 (in. H20)
//  Exhaust System
2” NPT
178–279 (7–11)
Gas Temp. (Stack): °C (°F)
Gas Volume at Stack
Temp: m3/min (CFM)
Maximum Allowable
Back Pressure: kPa (in. H20)
//  Fuel Consumption (NG-1000 BTU/ft3 / LP-2500 BTU/ft3)
At 100% of Power Rating: m3/hr (ft3/hr)
At 75% of Power Rating: m3/hr (ft3/hr)
At 50% of Power Rating: m3/hr (ft3/hr)
NG
59.9 (2,115)
46.7 (1,648)
32.8 (1,157)
LPG
19.9 (704)
17 (600)
11.5 (404)
694 (1,281)
38.8 (1,371)
2.5 (10.25)