English
Language : 

GS200-6S Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – GAS GENERATOR SET
GAS GENERATOR SET
GS200-6S
200 kWe /60 Hz /Standby
208 - 600V
(Reference GP175N6S for Prime Rating Technical Data)
SYSTEM RATINGS
Standby (NG)
Standby (LP)
GS200N6SGA
GS200L6SGA
Voltage (L-L)
Phase
PF
Hz
Natural Gas
Ratings: Amps
Natural Gas
Ratings: kW/kVA
LP Gas
Ratings: Amps
LP Gas
Ratings: kW/kVA
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
240V**
1
1.0
60
750
180/180
541
130/130
425
433CSL6216
130 °C/40 °C
12 LEAD ZIG-ZAG
* Consult the factory for alternate configuration.
** UL 2200 Offered
GS200N6SDA
GS200L6SDA
240V**
1
1.0
60
750
180/180
541
130/130
370
432PSL6228
130 °C/40 °C
4 LEAD
GS200N6SPA
GS200L6SPA
208V**
3
0.8
60
GS200N6SJA
GS200L6SJA
240V**
3
0.8
60
GS200N6SRA
GS200L6SRA
480V**
3
0.8
60
694
601
300
200/250
200/250
200/250
451
390
195
130/162
130/162
130/162
608
432CSL6210
130 °C/40 °C
12 LEAD LOW WYE
608
432CSL6210
130 °C/40 °C
12 LEAD HI DELTA
809
432CSL6210
130 °C/40 °C
12 LEAD HI WYE
GS200N6SNA
GS200L6SNA
600V**
3
0.8
60
240
200/250
156
130/162
720
432PSL6246
130 °C/40 °C
4 LEAD WYE
CERTIFICATIONS AND STANDARDS
//  Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//  UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
//  Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for
Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//  Power Rating
- Accepts Rated Load in One Step Per NFPA 110