DRC-60 Datasheet, PDF (4/5 Pages) Mean Well Enterprises Co., Ltd. – 60W Single Output with Battery Charger (UPS Function)
60W Single Output with Battery Charger (UPS Function)
DRC-60 series
Suggested Application
1.Backup connection for AC interruption
(1) Please refer to Fig1.1 for suggested connection.
The power supply charges the battery and provides energy to the load at the same time when AC mains is OK.
The battery starts to supply power to the load when AC mains fails.
A : 12V
B : 24V
Battery
+-
Bat+
Bat-
Load
+-
V+
V-
DC OK
+
+V ADJ
Fig 1.1 Suggested system connection
2.Alarm signal for AC OK and battery low
(1) Alarm Signal is sent out through " AC OK " & " Battery Low " pins via relay contact.
(2) An external voltage source is required for this function. The maximum applied voltage is 30V and the maximum sink current is 1A. Please refer to Fig 2.2.
(3) Table2.1 explains the alarm function built in the power supply
(4) AC OK signal (RL1,referring to Block Diagram) will go into hiccup mode when the overload protecton is activated.
Function
AC OK
Description
The signal is "Low" when the power supply turns ON.
The signal turns to be "High" when the power supply turns OFF.
The signal is "Low" when the voltage of battery is under A:11V, B:22V.
Battery Low
The signal is "High" when the voltage of battery is above A:11V, B:22V.
Output of alarm
Low or short
High or open (External applied voltage 30V max.)
Low or short
High or open (External applied voltage 30V max.)
Table 2.1 Explanation of alarm signal
AC OK (Battery low)
R
External voltage sorece (V) and resistor (R)
V
(The max. Sink is 1A and 30V)
Fig 2.2 Internal circuit of AC OK (Battery Low), via relay contact