English
Language : 

DRC-60 Datasheet, PDF (2/5 Pages) Mean Well Enterprises Co., Ltd. – 60W Single Output with Battery Charger (UPS Function)
60W Single Output with Battery Charger (UPS Function)
DRC-60 series
SPECIFICATION
MODEL
DRC-60A
DRC-60B
OUTPUT NUMBER
CH1
CH2
CH1
CH2
DC VOLTAGE
13.8V
13.8V
27.6V
27.6V
RATED CURRENT
2.8A
1.5A
1.4A
0.75A
CURRENT RANGE
0 ~ 4.3A
--------
0 ~ 2.15A
--------
RATED POWER
59.34W
59.34W
RIPPLE & NOISE (max.) Note.2 120mVp-p
OUTPUT
VOLTAGE ADJ. RANGE CH1:12 ~ 15V
--------
200mVp-p
CH1:24 ~ 30V
--------
VOLTAGE TOLERANCE Note.3 ±1.0%
--------
±1.0%
--------
LINE REGULATION
±0.5%
--------
±0.5%
--------
LOAD REGULATION
±0.5%
--------
±0.5%
--------
SETUP, RISE TIME Note.4 400ms, 50ms/230VAC 800ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.) 50ms/230VAC 10ms/115VAC at full load
VOLTAGE RANGE
90 ~ 264VAC 127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE 47 ~ 63Hz
INPUT EFFICIENCY (Typ.)
86%
88%
AC CURRENT (Typ.)
1.3A/115VAC 0.8A/230VAC
INRUSH CURRENT (Typ.) COLD START 30A/115VAC 60A/230VAC
OVERLOAD
105 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
PROTECTION
OVER VOLTAGE
CH1:14.49 ~ 18.63V
CH1:28.98 ~ 37.26V
Protection type : Shut down o/p voltage, re-power on to recover
BATTERY CUT OFF
10±0.5V
20±1V
AC OK
FUNCTION
BATTERY LOW
Relay contact output, ON : AC OK ; OFF : AC Fail ; max. rating : 30V/1A
Relay contact output, OFF : Battery OK ; ON : Battery Low ; max. rating : 30V/1A
Battery low voltage : < 11V
Battery low voltage : < 22V
WORKING TEMP.
-30 ~ +70℃ (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT
±0.03%/℃ (0 ~ 50℃) on CH1 output
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS UL60950-1, TUV EN60950-1 approved
SAFETY & WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
EMC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
(Note 5)
EMC EMISSION
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61204-3, light industry level, criteria A
MTBF
504.1K hrs min. MIL-HDBK-217F (25℃)
OTHERS DIMENSION
40*90*100mm (W*H*D)
PACKING
0.3Kg; 42pcs/13.6Kg/0.82CUFT
NOTE
℃







File Name:DRC-60-SPEC 2014-10-22