SOFTWARE CONFIGURATION cont.
SYSTEM CONFIGURATION MENU—VOLUME AND LEVEL
This menu is used to select the measurement units and con-
figure the system to measure Volume & Level. Refer to page
15 for Level Only applications or page 20 for Flow & Level
applications.
Following is a step-by-step procedure for using the Volume
& Level menu. It is assumed that you are starting from the
RUN mode.
System Configuration Menu (Volume and Level)
Display
Keystroke
Comment and/or Additional Keystrokes
Magnetrol Int’l
xxxx units
Press ENT
At start up, the unit is in the run mode displaying Magnetrol Int’l. Pressing ENT
allows you to enter the main menu.
Measured Values
ENT to Select
Press
Allows you to enter the System Config menu.
System Config
Press ENT
Enters the first display (Level Units) of System Config menu.
Level Units
Inches
Press ENT or
If inches are the desired Level Units press to continue to the next item. To
change units, press ENT and to select Feet, Centimeters, or Meters. Press ENT
to select desired Level Units.
Enter Password
(if units changed)
Enter Valid Password
(factory default is 300)
Entering a valid password and pressing ENT sets your unit selection and
continues on to the next item.
Mode Setup
Level Only
Press ENT
Then press then ENT to change to Volume and Level mode.
Volume Units
Cubic Feet
Press ENT or
If cubic feet are the desired Volume Units, press to continue to the next item.
To change units, press ENT and to select cubic inches, gallons, milliliters, or
liters. Press ENT to select desired Volume Units.
Vessel Type
Rectangular
Press ENT or
Press ENT, , then ENT to change present setting. You may select Rectangular,
Horiz/Flat, Horiz/Ellip, Horiz/Sphere, Spherical, Verti/Flat, Verti/Ellip, Verti/Sphere,
Verti/Conical or Custom Table (Refer to Figure 12 for Custom Table). If the
present setting is correct (Rectangular), press ENT, input vessel dimensions, and
then press to continue to next selection.
Radius=
xxxx units
(Vessel Dependent)
Enter value and press ENT
The values requested may vary depending on the type of vessel selected. Refer
to vessel drawing for proper dimensions.
Width=
xxxx units
(Vessel Dependent)
Enter value and press ENT
The values requested may vary depending on the type of vessel selected. Refer
to vessel drawing for proper dimensions.
Length=
xxxx units
(Vessel Dependent)
Enter value and press ENT
The values requested may vary depending on the type of vessel selected. Refer
to vessel drawing for proper dimensions.
Range Setting
xxxx units
Press ENT or
Press ENT to change the range setting. If setting is correct, press to continue
to Span Settings.
NOTE: It is recommended to use Manual Set (as opposed to Auto Set) when changing the range or span settings.
Manual Set
xxxx units
Press ENT or
Press ENT to manually set the range setting. An will appear in the bottom line
of the display. This allows you to change the range value. Measure the distance
from the face of the transducer to the maximum distance to be measured. Enter
value and press ENT. If Auto Set is preferred press .
Auto Set (If chosen)
xxxx units
Press ENT or
The liquid surface must be at the maximum distance to be measured. Check to
see that the distance being displayed is correct. When you press the ENT key,
that distance will be set as your range and the program will continue on to the
next selection. To continue without making changes press .
NOTE: The span value is automatically set ONLY when the entered range value has decreased from its previous value.
Span Setting
xxxx units
Press ENT or
Value shown will be 18 inches less than the range setting. This is the maximum
span value available. To reduce the span press ENT. If the present setting is
correct press to continue to Previous Menu.
Manual Set
xxxx units
Press ENT or
Press ENT to manually set the span setting. Measure the distance from the
maximum range that was set to the highest point to be measured. Enter value
and press ENT. If Auto Set is preferred press .
Auto Set (If chosen)
xxxx units
Press ENT or
The liquid surface must be at the highest level to be measured. Check to see
that the level being displayed is correct. When you press the ENT key, that
measurement will be set as your span and the program will continue on to the
next selection. To continue without changes press .
Previous Menu
ENT to select
Press ENT
Pressing the ENT key will set all values and return to System Config. Press DEL
to return to the run mode.