300-R010-45G Datasheet, PDF (15/36 Pages) Magnetrol International, Inc. – Echotel® Model 300/301 Ultrasonic Non-Contact Transmitter For Level/Volume/Open Channel Flow
SOFTWARE CONFIGURATION cont.
MEASURED VALUES MENU
The Measured Values Menu can be accessed by pressing the
ENT key from the run mode. You may scroll though the
measured values by using the up and down arrows. The
items displayed in the Measured Values Menu will differ
depending on whether Level Only, Vol & Level, or Flow &
Level has been selected in the System Config section
described later in this manual.
Display
Magnetrol Int’l
xxxx units
Measured Values
Level
xxxx units
Distance
xxxx units
Loop
xxxx
Temperature
xxxx F
Previous Menu
ENT to select
Keystroke
Measured Values Menu
Comments or Additional Keystrokes
Press ENT
Enters the Measured Values Menu.
Press ENT
Press
Press
Press
Press
Press ENT,
, or DEL
Displays the first item (Level) in the Measured Values Menu.
Indicates the level of material in the vessel. Pressing allows you to continue
to the next menu item.
Indicates the distance from the face of the transducer to the target. Pressing
allows you to continue to the next menu item.
Indicates the milliamp current loop output. Pressing allows you to continue to
the next menu item.
Indicates the air temperature at the transducer. The temperature units are in ° F or ° C
depending upon whether English or metric units of level are chosen. Pressing
allows you to continue to the next menu item.
Pressing will cycle back to the Level display, or press ENT or DEL to continue
to the next configuration item.
SYSTEM CONFIGURATION MENU—LEVEL ONLY
This System Configuration menu is used for basic setup of
the unit. Refer to pages 13 and 14 for the complete menu
layout. The Model 300/301 is capable of being configured in
three different modes of operation—Level Only, Volume &
Level, or Flow & Level. The System Configuration Menu is
for selecting the measurement units and calibrating the sys-
tem to measure Level Only (refer to page 15-16), Volume &
Level (page 17), or Flow & Level (page 20).
The following table is a step-by-step procedure for using the
Level Only menu. It is assumed that you are starting from the
RUN mode.
Display
Magnetrol Int’l
xxxx units
Measured Values
ENT to Select
System Config
Level Units
Inches
Enter Password
(if units changed)
Mode Setup
Level Only
Keystroke
Press ENT
System Configuration Menu (Level Only)
Comment and/or Additional Keystrokes
At start up, the unit is in the run mode displaying Magnetrol Int’l. Pressing ENT
allows you to enter the main menu.
Press
Allows you to enter the System Config menu.
Press ENT
Press ENT or
Enter Valid Password
(factory default is 300)
Press
Enters the first display (Level Units) of System Config. menu.
If inches are the desired Level Units press to continue to the next item. To
change units, press ENT and to select Feet, Centimeters, or Meters. Press ENT
to select desired Level Units.
Entering a valid password and pressing ENT sets your unit selection and
continues on to the next item.
Press to continue to the next item. This section covers a Level Only config-
uration. Turn to page 17 if a Volume & Level configuration is desired, or page 20
for Flow & Level.
Continued on page 16
15