3.0 Reference Information
3.1 Troubleshooting
3.1.1 No Signal with Level Change
1. Check power and control circuit wiring.
2. Check fail-safe switch position.
3. Check calibration.
4. Check for proper ground reference particularly in non-
metal tanks.
If removal of electronic module is necessary:
1. Loosen mounting screws. Refer to Figure 5.
2. Slowly raise electronic module exposing probe wiring.
3. Disconnect probe and guard leads. Remove electronic
module.
3.1.2 Switch Chatter
1. Check for turbulence. If turbulence is present, increase
time delay.
2. Check for low voltage.
3. Check for proper ground reference.
4. Check for proper DIP switch position.
NOTE: If these suggestions prove unsuccessful, consult factory.