Hydraulic Crimping Head 1673672- 1
408- 8910
NOTE
i
If SOLISTRAND terminal or splice sticks in the die after crimping, apply a rocking motion to remove it from the die.
ACCEPT
1
Terminal
REJECT
1
4
4
2
Wire Range Stamped 3
6
Under Tongue
36
1
6
Parallel Splice
5
3
4
3
1
Wire Range Stamped 2
Under Tongue
4
1
6
4
1
5
4
3
6
Butt Splice
36
2
Wire Range
Stamped Here
2
Wire Range
Stamped Here
1 Crimps centered. Crimps may be off center BUT NOT
OFF END OF WIRE BARREL.
2 AWG wire size being used matches wire range stamped
on terminal or splice and tool.
3 Wire insulation does not enter wire barrel.
4 Conductor is visible through inspection hole of butt splice.
Conductor is flush with or extends slightly beyond end of
terminal wire barrel.
5 On parallel splices, conductor ends must be flush with or
extend slightly beyond end of barrel.
6 No nicked or missing conductor strands.
1 Crimped off end of splice or terminal wire barrel.
2 AWG wire size being used does not match wire range
stamped on terminal or splice and tool.
3 Wire insulation entered barrel of terminal or splice.
4 Conductor not inserted far enough in terminal or splice.
End of conductor must be visible through inspection hole
of butt splices, and be flush with or extend beyond end of
terminal wire barrel or parallel splice.
5 Excessive “flash” on terminal or splice indicates wrong
wire, splice, terminal or tooling combination was used, or
damaged dies.
6 Nicked or missing conductor strands.
Figure 5