English
Language : 

98-3100 Datasheet, PDF (1/2 Pages) Tyco Electronics – Definite Purpose Contactor 3-pole, 20-40 FLA AC Coil
Catalog 1308242
Issued 3-03 (PDF Rev. 3-04)
PRODUCTS UNLIMITED
Model 98 - 3100 series
Definite Purpose Contactor
3-pole, 20-40 FLA
AC Coil
File E75492
File EN60947-4-1:1991
IEC 947-4-1
Features
• 3-pole contactors.
• Industry-standard mounting plate.
• Optional interlock/auxiliary switches available.
• Manual test button is standard.
• Coil dust cover helps keep dust and dirt away from magnet and coil area.
• Double E magnet system provides optimal performance.
Contact Data @ 25°C
Arrangements: 3 Form X (3PST-NO-DM).
Maximum Ratings: See Contact Ratings Table.
Material: Silver Cadmium Oxide.
Coil Data @ 25°C
Voltage: 24 - 480 VAC, 50/60 Hz. See Coil Data Table below.
Insulation Class: UL Class B (130°C).
Duty Cycle: Continuous.
Contact Ratings
Full
Load
Amps
20
Number
of
Poles
3
25
3
Line
Voltage
240/277
480
600
240/277
480
600
Locked
Rotor
Amps
120
100
80
150
125
100
240/277
180
30
3
480
150
600
120
240/277
240
40
3
480
200
600
160
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that users also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Environmental Data
Temperature Range: Storage and Operating: -40°C – +65°C.
Flammability: UL 94-HB housing.
Mechanical Data
Contact Termination:
20, 25, 30 FLA Models
Type: #10-32 Screw with quad 0.250” (6.35 mm) quick connects.
Wire Size: 16-8 AWG (Stranding must be split for 8 AWG wire.)
Tightening Torque: 25 in.-lbs.
40 FLA Models
Type: Box Lug with dual 0.250” (6.35 mm) quick connects.
Wire Size: 14-4 Cu/Al AWG
Tightening Torque: 40 in.-lbs.
Coil Termination: Dual 0.250” (6.35 mm) quick connects, standard.
A 0.250” quick connect and a #6-32 screw, optional.
Arc Cover: Optional on 20-30 FLA models, standard on 40 FLA models.
Weight: 16 oz. (455 g) approximately
Resistive
Amps
Rating
30
30
30
35
35
35
40
40
40
50
50
50
Voltage
110/120
200/240
480/600
110/120
200/208
240/277
480
600
110/120
200/208
240/277
480
600
110/120
200/208
240/277
480
600
Maximum Horsepower
Single
Phase
1.5
3
-
2
-
5
-
-
2
-
5
-
-
3
-
7.5
-
-
Three
Phase
-
7.5
7.5
-
7.5
10
15
20
-
10
10
15
20
-
10
10
20
25
Coil Data
Nominal Coil Voltage
Maximum Pickup Volts
Drop-Out Volts Range
Nominal Inrush VA @ 50 Hz
Nominal Inrush VA @ 60 Hz
Nominal Sealed VA @ 50 Hz
Nominal Sealed VA @ 60 Hz
Nominal DC Resistance - Ohms
24
18
6 -15
60
53
6.0
5
7
120
88
20 - 70
60
53
6.0
5
180
208/240
177
40 - 140
60
53
6.0
5
720
277
220
65 - 185
60
53
6.0
5
950
480
384
150 - 270
65
53
6.0
5
3100
Dimensions are shown for
832 reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
Refer to inside back cover.