English
Language : 

LSP05_17 Datasheet, PDF (3/3 Pages) Littelfuse – LED Lighting Surge Protection Module > LSP05
Surge Protection Module
LED Lighting Surge Protection Module > LSP05
Typical Dimensions (mm)
Dimensions 56.0 ±0.5
Typical Dimensions (mm)
56.0 ±0.5
100 ±20
48.0 ±1.5
48.0±1.5
2x ø4.8±0.2
48.0±1.5
2x ø4.8±0.2
100 ±20
3 indication wires
all use the AWG22.
2.3 ±0.2
100 ±20
48.0 ±1.5
100 ±20 3 indication wires
all use the AWG22.
30.0 ±1.0
6 ±2
2.3 ±0.2 64.0 ±1.5
6 ±2
30.0 ±1.0
6 ±2
64.0 ±1.5
6 ±2
LSP05XXXXXP
LSP05XXXXXP
LSP05XXXXXPM
Notes:
LSP05XXXXXPM
1. Black: Line; White: Neutral; Green: Ground
(P/N with suffix X3333/X3316: Brown: Line; Blue: Neutral; Green-Yellow stripe: Ground)
2. Black: R1; Red: R2; Blue: R3
3. Wire Gauge: AWG14 wire Line in, AWG22 Wire for indication; Wire Length: 100mm or
customized
Part Numbering System
LSP 05 480LL P Xxxxx
Device Family
Littelfuse Surge Protection Module
Nominal Discharge
Current (In)
Operating Voltage
Connection mode
LL: for L,L,N/G
Blank: L-N, L-G, N-G
P or PM
(P: parallel connection; PM: parallel
connection and with monitor indication wire)
Other non-standard option:
X3333: with GND wire connection, available for
240Vac and 277Vac rating with CE Marking for
Class I earthed installation
Wire Color: Line: Brown, Neutral: Blue, Ground/P:
Green with yellow stripe
© 2016 Littel3fu3s1e6, I:nwc.ithout GND wire connection option
SpecificationWs iarreeCsuoblojerc: tLtionech: aBnrgoewwni,thNoeutuntroatli:ceB.lue
Revised: 05/09/16
Application/Installation Schematic
L
L
L
or N
N/G
G
L
AC/DC
N Power
Supply
+
-
LED Module
Parallel Connection
With LED indicating SPD status
- ON (green): SPD is online
- OFF: SPD needs replacement
R1
R2
SPD R3
LSP05xxxPM
NC
LED normally on
R
L
L
L
or N
N/G
G
L
AC/DC
N Power
Supply
+
-
LED Module
R1
Parallel Connection
With LED indicating SPD status
- OFF: SPD is online
SPD R2
R3
LSP05xxxPM
- ON (red): SPD needs replacement
LED normally off
R
Notes:
1. LED indicator and associated circuitry are not included in the module.
2. R1 must be capped off by wire nut when not connected (NC).
3. R1 and R2 are AC line voltage (hot); R3 is AC neutral voltage.
4. R2 voltage is cut off when SPD needs replacement.
5. R is current limiting resistor; it resistance/wattage is determined by AC line voltage
and desired current driving LED. Example: AC line voltage 240V, LED: 1.6mA, resistor:
150Kohm/0.5W.
L
L
L
or N
N/G
G
AC/DC
L Power
N Supply
+
-
LED Module
Parallel Connection
SPD
L
L
AC/DC
+
N
N Power
-
G
Supply
LED Module
Parallel Connection
(for Class II Unearthed)
SPD
~X3316
3