LSP05, LSP05_17 Datasheet, PDF (1/3 Pages) Littelfuse, Datasheet search site for Electronic Components and Semiconductors, integrated circuits, diodes and other semiconductors.">
 English
Language : 

LSP05_17 Datasheet, PDF (1/3 Pages) Littelfuse – LED Lighting Surge Protection Module > LSP05
Surge Protection Module
LED Lighting Surge Protection Module > LSP05
LSP05 Module Series
RoHS
Description
The Littelfuse LSP05 thermally protected Surge Protective
Device is a self-protected device which is specially designed
to be used in outdoor and commercial LED lighting fixtures
for transient overvoltage protection. It is constructed with
Littelfuse thermally protected varistor technology. Its built-in
thermal disconnect function provides additional protection
to prevent catastrophic failure and fire hazard even under the
extreme circumstances of varistor end-of-life or sustaining
over voltage conditions. The LSP05 facilitates customer’s
product compliance to IEEE C62.41.2 Location Category C
Low and US Dept of Energy MSSLC Model Spec.
Agency Approvals
Agency
Standard
UL1449
Agency File Number
E320116
Applications
• Outdoor and Commercial
LED Lighting
• Roadway lighting
• Traffic lighting
• Digital signage
• Wash wall lighting
• Parking garage/lot lighting
• Flood lighting
• Tunnel lighting
• Street lighting
Additional Information
Datasheet
Resources
Samples
Features
• Maximum Discharge
connected modules
Current, 10kA, 8/20us
• UL 1449 Type 4
• Meets ANSI C82.77-
Component Assembly
5-2015: Location
Recognition (Type 4CA)
Category CM, 10kV/5kA, • IEC61643-11 Class II/
1.2/50µS-8/20µS
EN61643-11 Type
Combination Wave.
2 Compliant1
• Meets IEEE C62.41.2:
• Compact form factor
Location Category CLow, (48x48x30mm) with
6kV/3kA, 1.2/50µS-8/20µS mounting tabs
Combination Wave.
• 240Vac and 277Vac
• Meets US Dept.
voltage ratings are
of Energy MSSLC
available for Class I
Model Spec.
and Class II installation
• Parallel connected
based on IEC luminaire
SPD device
protection classes
• Thermally protected
• CE - Meets the
Varistor technology
requirements of Low
• IP66 Water-proof
and Dust-proof
Voltage and RoHS
European Directives.
• Indication wire lead
options for Parallel
Notes:
1. Self-declared compliance.
Absolute Maximum Ratings
• For ratings of individual members of a series, see Device Ratings and Specifications chart
LSP05 Series
Units
Continous:
Steady State Applied Voltage:
Transient:
Max AC Voltage Range (VM(AC)RMS)
150 to 510
V
Maximum Discharge Current 8/20μs Waveform (Imax)
10,000
A
Nominal Discharge Current 8/20µs Waveform (In)
5,000
A
Operating Ambient Temperature Range (TA)
-45 to +85
°C
Storage Temperature Range (TSTG)
-45 to +125
°C
Isolation Voltage Capability (When the thermal disconnect opens)
600
V
Insulation Resistance
>1,000
MΩ
CAUTION: Stresses above those listed in "Absolute Maximum Ratings" may cause permanent damage to the device. This is a stress only rating and operation of
the device at these or any other conditions above those indicated in the operational sections of this specification is not implied.
© 2016 Littelfuse, Inc.
1
Specifications are subject to change without notice.
Revised: 05/09/16