English
Language : 

CP2725AC54Z Datasheet, PDF (2/8 Pages) Lineage Power Corporation – Compact Power Line Front-End Power Supply
Data Sheet
Compact Power Line
CP2725AC54 Front-End Power Supply
Specifications
Input
Parameter
Min
Startup Input Voltage
1200W Operation
2725W Operation
Operating Voltage Range
1200W Configuration 85
2725W Configuration 175
2725W Configuration 150
Permitted Excursions
275
Surges
300
Input Frequency
47
Input Current
Inrush Transient
Input Leakage Current
Power Factor
0.96
Efficiency
88
91
Typ
120/200/240
200/240
13.3
11.2
15.6
13.1
25
2.5
0.98
90
93
Holdup Time
15
20
Max Units Notes
The power supply automatically configures its
90
operating mode based on the voltage level it
180
reads on first turn ON. (This information is
retained as long as internal bias is maintained.)
275
275
Vac
If started within low input line range.
If started within high input line range.
175
Will derate to 80% of full load; will shutdown
below 150Vac.
300
May not meet all requirements, but will
maintain output regulation.
325
May shut down but will not get damaged.
66
Hz
At 100 Vac
A
At 120 Vac
At 200 Vac
At 240 Vac
35
Apk
Measured at 25°C for all line conditions; does
not include X-Capacitors charging.
mA Measured at 265Vac, 60Hz
From 50% to 100% load.
%
At 100 Vac with Vout > 52V and Pout > 50%.
At 230 Vac with Vout > 52V and Pout > 50%.
Measurement starts at zero crossing of the ac
voltage. Alarm issued via PFW signal going LO
ms
5 ms prior to output voltages going out of limits.
Measurements made at 75% full load and
voltage allowed to decay to 40V.
For loads below 1200W.
Main Output
Parameter
Maximum Output Power
Default Set point
Set point Accuracy
Overall Regulation
Set point adjustment range
Output Current
Current Share
Proportional Current Share
Min
Typ
Max Units Notes
1200
2725
W
At low-line input from 100-120Vac nominal.
At high-line input from 200-240Vac nominal.
54
Vdc Output floats with respect to frame ground.
-1
+1
%
-2
+2
%
Includes all variations due to specified load
range, drift, and environmental conditions.
44
58
Vdc Hardware configured via margin pin
42
58
Vdc Set either by I2C or RS4851
1
22.2
At 1200W, 54V and 100-120Vac.
1
50.5
A At 2725W, 54V and 200-240Vac.
1
53.4
At 2725W, 52V and 200-240Vac
-5
5
%FL
Compared to the average output current
delivered by a set of rectifiers. Loads > 50% FL
10
%FL
Among CP rectifiers of different output
capacities. Loads > 50% FL
1 I2C settings are not retained in case of loss of bias to the control DSP. However, RS485 settings are retained when bias is lost.
Lineage Power
2