English
Language : 

HAZ4000-SB_07 Datasheet, PDF (3/3 Pages) LEM – Current Transducers
Dimensions HAZ 4000..20000-SB (in mm. 1 mm = 0.0394 inch)
FUJICON F2023A
6
1
6543 21
N.C. GND OUTPUT 0V -Vc +Vc
HAZ 10000-SB
250 +/-1.5
235
116621+±±/-121
200
Connection Circuit
HAZxxx-SB
1
+Vc
2
-Vc
3
0V
4-D6
RL=10K ohm
4
OUTPUT
5
GND
N.C.
6
Operation Principle
Terminal
M5
1...+Vc
2...-Vc
3...0V
4...OUTPUT
5...GND
Ip
6...N.C.
General tolerance +/-0.5
+Vc
Output
0V
-Vc
Mechanical characteristics
Safety
• General tolerance
• Aperture for primary conductor
• Transducer fastening
• Recommended fastening torque
• Connection of secondary
± 0.5 mm
162 mm x 42 mm
(± 2 mm)
4 x M5
(not supplied)
< 5 Nm
Fujicon F2023A
(6 terminals)
This transducer must be used in electric/electronic equipment
with respect to applicable standards and safety requirements
in accordance with the following manufacturer's operating
instructions.
Caution, risk of electrical shock
Remarks
• Temperature of the primary conductor should not exceed
120°C.
• VOUT is positive when IP flows in the direction of the arrow.
When operating the transducer, certain parts of the module can
carry hazardous voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious
damage.
This transducer is a built-in device, whose conducting parts
must be inaccessible after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
070219/8
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 3/3
www.lem.com