English
Language : 

HAZ4000-SB_07 Datasheet, PDF (1/3 Pages) LEM – Current Transducers
Current Transducers HAZ 4000..20000-SB
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 4000..20000 A
VOUT= ± 10 V
Electrical data
Primary nominal
DC current or AC peak
IPN (A)
4000
6000
10000
12000
14000
20000
Primary current
measuring range
IPM (A)
± 4000
± 6000
± 10000
± 12000
± 14000
± 20000
Type
HAZ 4000-SB
HAZ 6000-SB
HAZ 10000-SB
HAZ 12000-SB
HAZ 14000-SB
HAZ 20000-SB
RoHS since
date code
46177
46177
46177
planned
planned
planned
V
Supply voltage (± 5 %)
C
± 15
V
IC
Current consumption
± 30
mA
Î
Overload capability
P
30,000
A
RIS
Isolation resistance @ 500 VDC
> 1000 MΩ
VOUT
Output voltage (Analog) @ ± IPN, RL = 10 kΩ, TA = 25°C ± 10
V
ROUT
Output internal resistance
approx.100
Ω
RL
Load resistance
> 10
kΩ
Accuracy - Dynamic performance data
X
εL
VOE
VOH
TCVOE
TCVOUT
tr
t
ra
di/dt
BW
Accuracy @ I , T = 25°C (excluding offset)
PN A
Linearity error 1) (0 .. ± IPN)
Electrical offset voltage @ TA = 25°C, IP = 0
Hysteresis offset voltage @ IP = 0;
after an excursion of 1 x IPN
Temperature coefficient of VOE
Temperature coefficient of VOUT (% of reading)
Response time to 90% of IPN step
Reaction time @ 10% of I
PN
di/dt accurately followed
Frequency bandwidth, ± 3 dB, small signal 2)
<±1
%
< ± 0.5 % of IPN
< ± 50
mV
< ± 12.5
<±1
< ± 0.05
< 10
<2
> 50
DC .. 3
mV
mV/K
%/K
µs
us
A/µs
kHz
Features
• Hall effect measuring principle
• Galvanic isolation between primary
and secondary circuit
• Instantaneous voltage output
• Isolation voltage 12kV Rms /50 Hz
/1 m i n
• Low power consumption
• Package in PBT meeting UL 94-V0
• Instantaneous voltage output
Advantages
• Easy installation
• Small size and space savings
• Only one design for wide current
ratings range
• High immunity against external
interference
Applications
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Power supplies for welding and
telecom applications.
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
Housing PBT 30% glassfiber
m
Mass
Standard 3)
- 25 .. + 85 °C
- 30 .. + 90 °C
Application domain
• Industrial
approx. 6
kg
EN 50178:1997
Notes : 1) Linearity data exclude the electrical offset.
2) To avoid excessive core heating
3) Please consult characterisation report for more technical details and
application advice.
070219/8
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3