English
Language : 

HO15-NP0000 Datasheet, PDF (12/15 Pages) LEM – Current Transducer
HO-NP/SP33-1000 SERIES
Application information
Total primary resistance
The primary resistance is 0.36 mΩ per conductor at 25 °C.
In the following table, examples of primary resistance according to the number of primary turns.
Number of
primary turns
Primary resistance
current rms
RP [ mΩ ]
1
0.12
2
0.54
3
1.18
Recommended connections
13 12 11 OUT
IN 8 9 10
13 12 11 OUT
IN 8 9 10
13 12 11 OUT
IN 8 9 10
Primary nominal current
IPN [ A ]
8
15
25
4
7.5 12.5
2.67
5
8.33
Definition of typical, minimum and maximum values
Minimum and maximum values for specified limiting and safety conditions have to be understood as such as well as values
shown in “typical” graphs. On the other hand, measured values are part of a statistical distribution that can be specified by an
interval with upper and lower limits and a probability for measured values to lie within this interval.
Unless otherwise stated (e.g. “100 % tested”), the LEM definition for such intervals designated with “min” and “max” is that
the probability for values of samples to lie in this interval is 99.73 %. For a normal (Gaussian) distribution, this corresponds
to an interval between -3 sigma and +3 sigma. If “typical” values are not obviously mean or average values, those values are
defined to delimit intervals with a probability of 68.27 %, corresponding to an interval between -sigma and +sigma for a normal
distribution.
Typical, maximal and minimal values are determined during the initial characterization of a product.
Remark
Installation of the transducer must be done unless otherwise specified on the datasheet, according to LEM Transducer Generic
Mounting Rules. Please refer to LEM document N°ANE120504 available on our Web site: Products/Product Documentation.
17September2013/Version 2 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
Page 12/15