English
Language : 

HY5-P_06 Datasheet, PDF (1/2 Pages) LEM – Current Transducers
Current Transducers HY 5..25-P
IPN = 5 .. 25 A
For the electronic measurement of currents : DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Electrical data
Primary nominal
current rms
IPN (A)
5
10
12.5
15
20
25
Primary current,
measuring range
IPM (A)
± 15
± 30
± 37.5
± 45
± 60
± 75
Primary
conductor
(mm)
∅ 0.7
∅ 1.1
∅ 1.4
∅ 1.4
2 x ∅ 1.2 1)
2 x ∅ 1.4 1)
Type
HY 5-P
HY 10-P
HY 12-P
HY 15-P
HY 20-P
HY 25-P
RoHS since
date code
45260
45286
45264
45276
46097
45269
VC
IC
ÎP
V
d
Vb
R
IS
VOUT
R
OUT
RL
Supply voltage (± 5 %) 6)
± 12 .. 15 V
Current consumption
± 10
mA
Overload capability (1 ms)
50 x IPN
Rms voltage for AC isolation test, 50 Hz, 1 min
2.5
kV
Rated isolation voltage rms
500 2)
V
Isolation resistance @ 500 VDC
> 1000 MΩ
Output voltage (Analog) @ + IPN, RL = 10 kΩ, TA = 25°C ± 4
V
Output internal resistance
100
Ω
Load resistance
>1
kΩ
Accuracy - Dynamic performance data
X
εL
V
OE
VOH
TCVOE
TCVOUT
t
r
di/dt
BW
Accuracy @ I , T = 25°C (excluding offset)
PN A
Linearity error 3) (0 .. ± IPN)
Electrical offset voltage@ T = 25°C
A
Hysteresis offset voltage @ IP = 0;
after an excursion of 1 x I
PN
Temperature coefficient of VOE
<±1
%
< ± 1 % of IPN
< ± 40
mV
< ± 15
typ. ± 1.5
max. ± 3
mV
mV/K
mV/K
Temperature coefficient of VOUT (% of reading)
Response time to 90% of I step
PN
di/dt accurately followed
< ± 0.1
<3
> 50
%/K
µs
A/µs
Frequency bandwidth 4) (- 3 dB)
DC .. 50 kHz
General data
TA
Ambient operating temperature
T
Ambient storage temperature
S
m
Mass
Standards 5)
- 10 .. + 80 °C
- 25 .. + 85 °C
< 14
g
EN 50178: 1997
Features
• Hall effect measuring principle
• Galvanic isolation between primary
and secondary circuit
• Isolation voltage 2500 V~
• Compact design for PCB mounting
• Low power consumption
• Extended measuring range (3 x IPN)
• Insulated plastic case recognized
according to UL 94-V0.
Advantages
• Easy mounting
• Small size and space saving
• Only one design for wide current
ratings range
• High immunity to external
interference.
Applications
• Static converters for DC motor drives
• Switched Mode Power Supplies
(SMPS).
• AC variable speed drives
• Uninterruptible Power Supplies
(UPS)
• Battery supplied applications
• General purpose inverters
Application domain
• Industrial
Notes : 1) Conductor terminals are soldered together.
2) Pollution class 2, overvoltage category III.
3) Linearity data exclude the electrical offset.
4) Please refer to derating curves in the technical file to avoid excessive
core heating at high frequency.
5) Please consult characterisation report for more technical details and
application advice.
6) Operating at ±12V ≤ Vc < ±15V will reduce measuring range.
061027/8
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/2
www.lem.com