English
Language : 

HAT200-S Datasheet, PDF (1/3 Pages) LEM – Current Transducer
Current Transducer HAT 200..1500-S
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 200..1500 A
VOUT = ± 4 V
Electrical data
Primary nominal
r.m.s. current
IPN (A)
200
400
500
600
750
800
1000
1200
1500
Primary current
measuring range 4)
IP (A)
± 600
± 1200
± 1500
± 1800
± 2250
± 2400
± 3000
± 3000
± 3000
VC
IC
R IS
VOUT
ROUT
R
L
Supply voltage (± 5 %) 4)
Current consumption
Isolation resistance @ 500 VDC
Output voltage @ ± IPN, RL = 10 kΩ, TA = 25°C
Output internal resistance
Load resistance
Accuracy-Dynamic performance data
X
εL
V
OE
VOH
ε VOT
TC
G
tr
f
Accuracy @ I , T = 25°C (without offset)
PN A
Linearity error 1) (0 .. ± IPN)
Electrical offset voltage, T = 25°C
A
Hysteresis offset voltage @ IP = 0;
after an excursion of 1 x I
PN
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Frequency bandwidth 2) (- 3 dB)
Type
HAT 200-S
HAT 400-S
HAT 500-S
HAT 600-S
HAT 750-S
HAT 800-S
HAT 1000-S
HAT 1200-S
HAT 1500-S
± 15
V
± 15
mA
> 1000 MΩ
±4
V
100
Ω
> 10
kΩ
< ± 1 % of I
PN
< ± 1 % of IPN
< ± 20
mV
< ± 10
mV
< ± 1 mV/K
< ± 0.1 %/K
<5
µs
DC .. 25 kHz
General data
T
Ambient operating temperature
A
- 10 .. + 80 °C
TS
Ambient storage temperature HAT 200-S, HAT 500..1500-S - 15 .. + 85 °C
HAT 400-S
- 25 .. + 85 °C
m
Mass
300
g
UL94 classification
V0
Features
• Hall effect measuring principle
• Galvanic isolation between primary
and secondary circuit
• Isolation voltage 3000 V
• Low power consumption
• Extended measuring range 3 x IPN
• Insulated plastic case recognized
according to UL 94-V0
Advantages
• Easy mounting
• Small size and space saving
• Only one design for wide current
ratings range
• High immunity to external
interference.
Applications
• DC motor drives
• Switched Mode Power Supplies
(SMPS)
• AC variable speed drives
• Uninterruptible Power Supplies
(UPS)
• Battery supplied applications
• Power supplies for welding
applications
Notes :
1) Linearity data exclude the electrical offset.
2) Please refer to derating curves in the technical file to avoid excessive
core heating at high frequency.
3) Please consult characterisation report for more technical details and
application advice.
4) Operating at ±12V ≤ Vc < ±15V will reduce the measuring range.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM Industrial
051011/9
Page 1/3
www.lem.com