CT5-T_06 Datasheet, PDF (1/3 Pages) LEM – Current Transducer | |||
|
Current Transducer CT 5 .. 25-T
For very accurate measurements of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
IPN = 5 .. 25 A
0632
Electrical data
Primary nominal
current
IPN (A r.m.s.)
Primary current,
measuring range
IP (A)
5
7.5
10
15
25
37.5
V
OUT
RL
C
L
tC
V
C
IC
Analog output voltage
Load resistance
Capacitance loading
Output short-circuit duration 1)
Supply voltage (± 5 %)
Current consumption
Conversion
ratio
K N (A/V)
5 A/5 V
10 A/ 5 V
25 A/5 V
Accuracy - Dynamic performance data
X
Overall accuracy @ I
G
PN
- 25°C .. + 70°C
VO
Offset voltage @ I P = 0
TA = 25°C
- 25°C .. + 70°C
f
Frequency bandwidth (- 3 dB) @ 10 % of I
PN
tr
Response time
General data
TA
Ambient operating temperature
T
Ambient storage temperature
S
m
Mass
Standards
Type
CT 5-T
CT 10-T
CT 25-T
5
V
> 500
â¦
â¤5
nF
â
s
± 15
V
30 + VOUT / RL mA
± 0.1
%
Max
± 0.4
mV
± 0.6
mV
DC .. 500
kHz
<1
µs
- 25 .. + 70
°C
- 40 .. + 85
°C
670
g
EN 50178 : 1996
Features
⢠Closed loop (compensated) current
transducer
⢠Insulated plastic case recognized
according to UL 94-V0
⢠Patent pending.
Advanced features
⢠f = 500 kHz
⢠X G = ± 0.1 % (- 25°C .. + 70°C).
Advantages
⢠Excellent accuracy
⢠Very good linearity
⢠Low temperature drift
⢠Optimized response time
⢠Wide frequency bandwidth
⢠No insertion losses
⢠High immunity to external
interference
⢠Current overload capability.
Applications
⢠AC variable speed drives and servo
motor drives
⢠Static converters for DC motor drives
⢠Battery supplied applications
⢠Uninterruptible Power Supplies
(UPS)
⢠Switched Mode Power Supplies
(SMPS)
⢠Power supplies for welding
applications.
Note :
1) If the short-circuit has a duration more than 1 s, the primary current of
the supply voltage must be interrupted for a short time to restore the
transducer to proper working order. The internal protection is done by
PTC resistors.
Application domain
⢠Industrial.
060927/0
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3