XP10-M Datasheet, PDF (2/2 Pages) Honeywell Solid State Electronics Center – Ten-Input Monitor Module
Wiring Diagrams
CONNECT MODULES TO
LISTED COMPATIBLE
CONTROL PANELS ONLY.
47K EOL
RESISTOR
ELR-47K
CLASS B IDC (TYPICAL)
POWER-LIMITED & SUPERVISED
FROM PANEL
OR PREVIOUS
DEVICE
TO NEXT
DEVICE
COMMUNICATION LINE, 32 VDC MAX.
SEE PANEL MANUAL FOR WIRE RESTRICTIONS.
CONNECT MODULES TO
LISTED COMPATIBLE
CONTROL PANELS ONLY.
CLASS A IDC (TYPICAL)
FROM PANEL
OR PREVIOUS
DEVICE
POWER-LIMITED
& SUPERVISED
TO NEXT
DEVICE
COMMUNICATION LINE, 32 VDC MAX.
SEE PANEL MANUAL FOR WIRE RESTRICTIONS.
52347w1.wmf
FIGURE 1:
Typical Initiating Device
Circuit Configuration —
Class B, Style B.
NOTE: Any number of UL-Listed con-
tact closure devices may be used.
DO NOT MIX fire alarm initiating and
supervisory devices on the same initiat-
ing device circuit. Install contact closure
devices per manufacturer’s installation
instructions.
52347w2.wmf
FIGURE 2:
Typical Fault-Tolerant
Initiating Device
Circuit Configuration —
Class A, Style D.
NOTE: Any number of UL-Listed contact
closure devices may be used.
DO NOT MIX fire alarm initiating and
supervisory devices on the same initiating
device circuit. Install contact closure
devices per manufacturer’s installation
instructions.
REMOVE SHUNT
FOR CLASS A.
FlashScan® and Notifier® are registered trademarks of Honeywell Interna-
tional Inc.
©2007 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-6923:A1 • 8/3/07