XP10-M Datasheet, PDF (1/2 Pages) Honeywell Solid State Electronics Center – Ten-Input Monitor Module | |||
|
XP10-M
Ten-Input Monitor Module
DN-6923:A1 ⢠H-352
General
The XP10-M ten-input monitor module provides an interface
between a control panel and normally open contact devices in
intelligent alarm systems such as pull stations, security con-
tacts, or flow switches.
The first address on the XP10-M is set from 01 to 150 and the
remaining modules are automatically assigned to the next nine
higher addresses. Provisions are included for disabling a maxi-
mum of two unused addresses.
The supervised state (normal, open, or short) of the monitored
device is sent back to the panel. A common SLC input is used
for all modules, and the initiating device loops share a common
supervisory supply and ground â otherwise each monitor oper-
ates independently from the others.
Each XP10-M module has panel-controlled green LED indica-
tors. The panel can cause the LEDs to blink, latch on, or latch off.
Addressable Devices
Features
⢠Ten addressable Class B or five addressable Class A initiat-
ing device circuits.
⢠Removable 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²)
plug-in terminal blocks.
⢠Status indicators for each point.
⢠Unused addresses may be disabled.
⢠Rotary address switches.
⢠Class A or Class B operation.
⢠FlashScan® or CLIP operation.
⢠Mount one or two modules in a BB-XP cabinet (optional).
⢠Mount up to six modules on a CHS-6 chassis in a CAB-3
Series, CAB-4 Series, EQ Cabinet Series, or BB-25 cabinet
(optional).
⢠Mounting hardware included.
Specifications
Standby current: 3.5 mA (SLC current draw with all addresses
used; if some addresses are disabled, the standby current
decreases).
Alarm current: 55 mA (assumes all ten LEDs solid ON).
Temperature range: 32°F to 120°F (0°C to 49°C) for UL appli-
cations; â10°C to +55°C for EN54 applications.
Humidity: 10% to 85% noncondensing for UL applications; 10%
to 93% noncondensing for EN54 applications.
Dimensions: 6.8" (172.72 mm) high x 5.8" (147.32 mm) wide x
1.25" (31.75 mm) deep.
Shipping weight: 1.1 lb. (0.499 kg) including packaging.
Mounting options: CHS-6 chassis, BB-25 cabinet, BB-XP cab-
inet, CAB-3 Series cabinet (see DN-3549), CAB-4 Series cabi-
net (see DN-6857), or EQ Cabinet Series (see DN-60229).
Wire gauge: 12 AWG (3.31 mm²) to 18 AWG (0.821 mm²).
Power-limited circuits must employ type FPL, FPLR, or FPLP
cable as required by Article 760 of the NEC.
XP10-M is shipped in Class B position; remove shunt for
Class A operation.
Maximum SLC wiring resistance: 40 or 50 ohms, panel
dependent.
6923xp10.jpg
Maximum IDC wiring resistance: 1500 ohms.
Maximum IDC voltage: 12 VDC.
Maximum IDC current: 1 mA.
Agency Listings and Approvals
The listings and approvals below apply to the XP10-M Ten-Input
Monitor Module. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may be
in process. Consult factory for latest listing status.
⢠UL Listed: file S3705.
⢠ULC Listed: file S635 (XP10-MA).
⢠CSFM approved: file 7300-0028:219.
⢠FM approved.
⢠MEA approved: file 43-02-E.
⢠Maryland State Fire Marshal approved: Permit #2106.
Product Line Information
XP10-M: Ten-input monitor module.
XP10-MA: Same as above with ULC Listing.
BB-XP: Optional cabinet for one or two modules. Dimensions,
DOOR: 9.234" (23.454 cm) wide (9.484" [24.089 cm] including
hinges), x 12.218" (31.0337 cm) high, x 0.672" (1.7068 cm)
deep; BACKBOX: 9.0" (22.860 cm) wide (9.25" [23.495 cm]
including hinges), x 12.0" (30.480 cm) high x 2.75" (6.985 cm);
CHASSIS (installed): 7.150" (18.161 cm) wide overall x 7.312"
(18.5725 cm) high interior overall x 2.156" (5.4762 cm) deep
overall.
BB-25: Optional cabinet for up to six modules mounted on
CHS-6 chassis (below). Dimensions, DOOR: 24.0" (60.96 cm)
wide x 12.632" (32.0852 cm) high, x 1.25" (3.175 cm) deep,
hinged at bottom; BACKBOX: 24.0" (60.96 cm) wide x 12.550"
(31.877 cm) high x 5.218" (13.2537 cm) deep.
CHS-6: Chassis, mounts up to six modules in a CAB-3 Series
(see DN-3549), CAB-4 Series (see DN-6857) cabinet, EQ Cabi-
net Series (see DN-60229), or BB-25.
DN-6923:A1 ⢠8/3/07 â Page 1 of 2
|
▷ |