GWACC Datasheet, PDF (4/4 Pages) Gamewell-FCI by Honeywell – Audio Command Center Voice Evacuation Control Panel
Two Speaker Circuits
Dual output zone, dual input circuit — tone/voice message (see Figure 2). This application example consists of one GWACC with two
speaker circuits and requires the installation of a second amplifier. This configuration is suitable for small facilities requiring no more than 50 watts
of output power and a 60-second fire evacuation message.
In this application example, the addressable FACP directs tone or voice messages to either of the speaker circuits via the control modules con-
nected to the CMD1 and CMD2 inputs. S3 DIP switches “1”, “2”, and “3” are set to OFF; this selection configures CMD1/CMD2 to direct the Fire
Message to the Auditorium Speakers or Classroom Speakers. The S5 DIP switches “5” and “6” are set to ON; these contact closures activate
CMD1 (switch “5”) and CMD2 (switch “6”) inputs.
In this application example, the system may also be manually activated from the keypad. Press the Auditorium Speakers and/or Classroom
Speakers push-button(s), then press the Fire Message push-button. Alternately, use the microphone to make an announcement. To manually
deactivate a speaker circuit, press the activated (illuminated) output zone push-button.
Keypad Example
FIGURE 2:
Two Speaker Circuits,
Dual Output Zone,
Dual Input Circuit
NOTES:
1) *EOLR required only for Style
Y (Class B). 4.75K ohm, 1 watt,
P/N 75470.
2) Typical illustration of an addres-
sable Gamewell control panel and
addressable control modules. Re-
fer to manual for voltage ranges,
message control switch settings,
and command input specifica-
tions.
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
Specifications and wiring information are provided for information only and are
believed to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation.
For more information, contact Gamewell-FCI.
Page 4 of 4
GWACC CS-2504 09/01/06