English
Language : 

SP2R1224MC Datasheet, PDF (2/2 Pages) Gamewell-FCI by Honeywell – Wall Speaker/Strobes
Engineering Specifications
Speaker/Strobe shall be a System Sensor model _____ Listed to UL1480 and UL
1971 and be approved for fire protective signaling systems. Speaker shall be
capable of operating at 25.0 or 70.7 nominal VRMS, and shall have a frequency
range of 400 – 4000 Hz. Speaker shall have power taps that are selected by DIP
switch. The strobe shall consist of a xenon flash tube with associated lens/re-
flector system and operate on either 12 volts or 24 volts. The strobe shall also
feature selectable-candela output, providing options for 15 or 15/75 candela when
operating on 12 volts; and 15, 15/75, 30, 75, or 110 when operating on 24 volts.
The strobe shall comply with the Americans with Disabilities Act requirement for
visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating
voltage range.
Ordering Information
Description
Model No.
Candela
Setting
FWR
Operating
Current-
Strobe
(mA RMS)
DC Operating
Current-
Strobe
(mA RMS)
Red
White
12 V 24 V 12 V 24 V
15 112 64 127 59
Wall
15/75 135 74 127 69
Speaker/ SP2R1224MC SP2W41224MC 30
Strobe
75
93
90
158
160
110
208
209
Surf ace-
mount back BBS-SP2R
BBS-SP2W
box skirt
Sound Output
Pow er Tap
Se le ct ions :
Sound Output (UL
Reverberant
@ 10 ft./3.048 m):
Sound Output (UL
Anechoic
@ 10 ft./3.048 m):
2 Watt
84 dBA
87 dBA
1 Watt
81 dBA
84 dBA
1/2 Watt 1/4 Watt
78 dBA
75 dBA
81 dBA
78 dBA
Specifications
Input terminals
12 to 18 AWG (3.25 mm² to 0.51
mm²).
Dimensions
4.875" (12.383 cm) high x 8.25"
(20.955 cm) wide x 2.25" (5.715 cm)
deep.
Mounting
4" x 4" x 2.125" deep (10.16 x 10.16
x 5.398 cm) backbox.
Reversible strobe feature
Speaker/strobe is shipped in the
strobe-right-mounted position. For a
left-mounted strobe: Remove the
strobe screw and lift the strobe
assembly out of the rib slot. Rotate
the strobe 180° and remount to the
base.
Weight
3 lbs (1.361 kg).
Operating temperature, indoor
32°F to 120°F (0°C to 49°C).
Maximum humidity
85%.
Strobe operating voltages*
12 or 24 VDC and FWR unfiltered.
Operating voltage range:*
12V: 8 – 17.5V.
24V: 16 – 33 V. With Sync-
Circuit™ module MDL*: 12 V: 9 –
17.5 V. 24 V: 17 – 33 V.
Speaker input voltage
25.0 or 70.7 VRMS (nominal).
Speaker frequency range:**
400 – 4,000 Hz.
**The SP2 Series is UL Listed from
400 to 4,000 Hz but will provide an
output from 100 to 10,000 Hz.
Speaker power taps
1/4, 1/2, 1, and 2 watts.
U.S. Patent Numbers
5,593,569. 5,914,665. 5,850,178.
5,598,139. 6,049,446. 6,127,935.
6,522,261.
Gamewell
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell.com
A Honeywell Company
© 2004 Gamewell
Specifications and wiring information are provided for information only and are believed
to be accurate. Gamewell assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring instructions
shipped with the product shall always be used for actual installation. For more
information, contact Gamewell.
Page 2 of 2
SpectrAlert® Selectable Output Wall Speaker/Strobes CS-2452 10/21/04