GWF402 Datasheet, PDF (2/2 Pages) Honeywell Solid State Electronics Center – 2 and 4 Zone Conventional Fire Alarm Control Panels
Options
CAC-4
Used to convert Class B (Style B) IDCs to
Class A (Style D) and Class B (Style Y)
NACs to Class A (Style Z).
Mounts in FACP. Flex 404 only.
XRM-24
Second 100VA transformer for maximum
accessory power.
Mounts in FACP. Flex 404 only.
4XTMF
Transmitter module provides output for the
local energy municipal box transmitter and
alarm and trouble reverse polarity.
Mounts in FACP. Flex 402 & Flex 404.
4XZMF
Zone relay module provides Form-C relays:
Alarm Zones 1, 2, 3, 4, System Alarm,
Trouble. Mounts in FACP. Flex 404 only.
4XLMF
LED interface module supports the
GWSAN-404 remote annunciator,
supervises annunciator wiring for open
conditions. Mounts in FACP. Flex 404 only.
411UD
Four input/channel, dual line, digital alarm
communicator/transmitter (DACT). Input/
channels are compatible with normally
open relay contacts, are supervised and
fully programmable. Interfaces with public
switched telephone networks and
compatible with most central station receiv-
ers. Flex 404 only.
GWSAN-404 Remote annunciator mounts in single-gang
electrical box, provides LED indication of
Alarm Zones 1, 2, 3, 4; and System
Trouble. Flex 404 only.
Specifications
AC Power:
120 VAC, 50/60Hz, 2.3 A
Battery:
Max. charging circuit: 27.6 VDC@
0.8A Max. charger capacity: 18 Ah
(Two 7Ah batteries fit inside the FACP).
Initiating Device: Alarm zones 1 & 2
(Flex 402 / Flex 404)
Circuits (IDC): Alarm zones 3 & 4 (Flex 404 only)
Operation:
All zones Style B (Class B)
Power:
Class 2 Power-Limited circuitry
Operating
Voltage:
Nominal 20 VDC
Alarm Current: 15 mA minimum
Short Circuit
Current:
40 mA maximum
Standby Current: 4 mA
Maximum Loop
Resistance:
100 ohms
Notification:
One NAC: Flex 402
Two NACs:Flex 404
Circuits (NAC):
Operation:
Class B (Style Y)
Power:
Class 2 Power-Limited circuitry
Operating Voltage: Nominal 24 VDC
Specifications (Continued)
Circuits (NAC) (Continued)
Operating Voltage: Maximum signaling current: 2.5 A
total (5.0 A Flex 404 with an optional
transformer).
Maximum Line
Impedance:
1.5 volt drop
Form-C Relays: Trouble, Alarm
(Supervisory, Flex 404)
Contact Ratings: 2 A @ 30 VAC (resistive)
Resettable:
Operating voltage: nominal 24 VDC
Power:
Class 2 Power-Limited circuitry
Maximum
Available Current: 500 mA
Non-resettable: Operating voltage: nominal 24 VDC
Power:
Class 2 Power-Limited circuitry
Maximum
Available Current: 500 mA
Cabinet Dimensions:
Door:
15.3" x 14.7" x 0.3"
(39 x 37 x 1 cm)
Backbox:
15.0" x 14.5" x 3.0"
(38 x 37 x 8 cm)
Ordering Information
GWF402
Flex 402 conventional FACP, 2 zones,
120 VAC, red
GWF404
71252
Flex 404 conventional FACP, 4 zones,
120 VAC, red
EOL resistor, 4.7K ohm, ½ watt
52194
Flex 402 and Flex 404 Installation &
Operation Manual
Options:
CAC-4
XRM-24
4XTMF
4XZMF
4XLMF
411UD
PRO-411
GWSAN-404
BB-17F
Class A converter for initiating device
circuits and notification appliance cir-
cuits (cannot be used on Flex 402).
Transformer, expands NAC circuit
power from 3 to 5 amps.
Transmitter module for remote station
output or municipal box connection.
Relay module, four relays-by-zone,
alarm and trouble contacts, 24VDC.
Remote annunciator driver, 24 VDC,
supports GWSAN-404.
Four channel dual slave programmer
DACT, Form C relay and upload/
download capability; with enclosure,
requires PRO-411.
Programmer, use with 411UD,
411UDAC.
LED remote annunciator for Flex 404,
four alarms, one trouble
(requires 4XLMF).
Battery box, houses 2 batteries
(7-18 Ah max.).
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60292 Rev. D page 2 of 2
www.gamewell-fci.com