GWF402 Datasheet, PDF (1/2 Pages) Honeywell Solid State Electronics Center – 2 and 4 Zone Conventional Fire Alarm Control Panels | |||
|
Flex Series
GWF402 and GWF404
Description
The Flex 402 is a two zone fire alarm control panel (FACP)
and the Flex 404 is a four zone FACP. These control pan-
els provide reliable fire signaling protection for small to
medium-sized retail, office, multi-family, or other similar
commercial or institutional buildings.
The Initiating Device Circuits (IDCs) for the Flex Series
panels are categorized as Class 2 Power-Limited and
operate in Class B (Style B). Each panel is compatible with
the following types of conventional input devices.
⢠two-wire smoke detectors ⢠water flow devices
⢠four-wire smoke detectors ⢠tamper switches
⢠pull stations
In addition, each panel is compatible with other normally-
open contact devices. These devices include the System
Sensor i3⢠Series microprocessor-based detectors with
advanced features like drift compensation, maintenance
alert and freeze warning.
Note: For a listing of compatible devices, refer to the
Device Compatibility Document P/N: 52195.
The outputs include one notification appliance circuit
(NAC) on the Flex 402 and two NACs on the Flex 404.
NACs are categorized as Class 2 Power-limited and oper-
ate in Class B (Style Y). Each FACP has a Form-C Alarm
and Trouble relay and 24 VDC special applications resetta-
ble power. In addition, the Flex 404 has a Form-C Supervi-
sory relay and a special application non-resettable power
output. The FACP supervises wiring, AC voltage and bat-
tery level.
The activation of a compatible smoke detector or any nor-
mally-open fire alarm initiating device will do the following:
⢠Activate the audible and the visual signaling devices.
⢠Illuminate an indicating LED.
⢠Sound the piezo sounder at the FACP.
⢠Activate the FACP alarm relay.
⢠Operate any optional modules used to notify a remote
station.
⢠Initiate an auxiliary control function.
Two and Four Zone Conventional
Fire Alarm Control Panels
GWF402/G (left) and GWF404 (right)
Features
⢠Listed under UL® Standard 864, 9th Edition.
⢠Flex 402: Two Class B (Style B) IDC zones, one Class B
(Style Y) NACs.
⢠Flex 404: Four Class B (Style B) IDC zones, two Class B
(Style Y) NACs.
⢠Optional NAC Class A converter module (Flex 404).
⢠Offers the following NAC synchronization and
programmability features:
â ADA compliant strobe synchronization.
â ANSI audible signals as required by NFPA 72.
â Silence inhibit, auto-silence, non-silenceable.
â Selective Silence: mute horns, keep strobes lit.
â Temporal or steady signal.
⢠Displays silent or audible walk test from front keypad.
⢠Zone disable, alarm verification selectable per zone.
⢠Includes the following controls:
â Acknowledge
â Silence
â Alarm
â Walk Test
â Reset
â Zone enable/disable
⢠Contains the following LED indicators:
â Alarm
â Supervisory
â NAC fault
â System/Power Trouble
â Maintenance
â Trouble (one per zone)
â Walk Test
â Alarm Silence
â AC
â Charger/Battery/
â NAC/Zone Disable
Earth Fault (on pcb)
⢠Provides alarm verification.
⢠Uses a low AC voltage sense,automatic battery charger.
⢠Has a Piezo sounder for alarm, trouble, and supervisory.
i 3⢠is a trademark of Honeywell International Inc.
UL® is a registered trademark of Underwriterâs Laboratories Inc.
SIGNALING
MEA
Approved
FDNY:
S521 COA-# 366-04-E 7300-1703:0161
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA ⢠Tel: (203) 484-7161 ⢠Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2013 Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9021-60292 Rev. D page 1 of 2
|
▷ |