English
Language : 

XAL-53 Datasheet, PDF (1/2 Pages) Gamewell-FCI by Honeywell – Explosion-Proof Pull Station
September 1, 2006
CS-2506
XAL - 53
Explosion-Proof Pull Station
APPLICATIONS
XAL-53 fire alarm stations are suitable for:
• Hazardous areas due to the presence of flammable
gases or vapors, combustible dusts or easily ignit-
able fibers or flyings.
• Installation at petroleum refineries, chemical and pet-
rochemical plants, storage areas, and other process-
ing facilities where hazardous substances are
handled and stored.
• Areas where emergency control of fire alarm or sig-
nal circuits is required.
E50498
California
State Fire
Marshal
7150-1439:100
FEATURES
CE69
• Enclosure is made of copper-free aluminum alloy.
• Conduit openings are 3/4" (19.05 mm) NPT feed-
through.
• Red, textured powder epoxy paint finish is standard
on box and cover and provides high visibility for alarm
station.
• Universal (1) normally open and (1) normally closed
contact furnished standard.
• Bilingual nameplates included per CSA requirement.
• Internal ground screw is standard.
• Wiring range is #12 AWG through #24 AWG, solid
or stranded.
CSA
LR31085
XAL-53
Pull Ring
OPERATION
The alarm station is activated by lifting the front cover
and pulling down ring. This quick, easy-to-use two-
step process prevents unintentional operation. Opera-
tor is reset by depressing shaft and returning plate to
original position.
XAL-53
Dimensions
HAZARDOUS AREA
CLASSIFICATIONS
• Class I, Divison 1 and 2, Group C and D.
• Class II, Division 1 and 2, Group E, F, and G.
• Class III, Hazardous Locations.
• NEMA 7CD, 9EFG.
5274dim1.tif
AC
DC
CONTACT BLOCK
RATING
Volts
Make
Amperes
VA
Break
Amperes
VA
Continuous
Carrying
Amperes
Volts
Make
Break
Continuous
Carrying
Amperes
120
60 7200 6.0
720
10
125 1.10
10
240
30 7200 3.0
720
10
250 0.55
10
480
15 7200 1.5 720
10
600 0.20
10
600
12 7200 1.2 720
10
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
Specifications and wiring information are provided for information only and are believed
to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring instructions
shipped with the product shall always be used for actual installation.
For more information, contact Gamewell-FCI, a Honeywell company.