English
Language : 

GWF410 Datasheet, PDF (1/2 Pages) Gamewell-FCI by Honeywell – Flex 410 FACP, 10 zones, expandable to 20 and 30 zones, 120 VAC
Flex Series
GWF410
Description
10 Zone Expandable Conventional
Fire Alarm Control Panel
The Flex 410 is a ten zone fire alarm control panel (FACP)
expandable to twenty or thirty zones using optional CZM-
400 zone expander module(s). The Flex 410 is ideal for a
wide range of different sized installations such as hotels,
schools, correctional institutions, health care facilities,
small office buildings, and manufacturing plants.
Initiating device circuits (IDCs) for the Flex 410 can be pro-
grammed as either ten Class B (Style B) or five Class A
(Style D) circuits. This is expandable to either twenty Class
B (ten Class A), or thirty Class B (fifteen Class A) IDC cir-
cuits. The panel is compatible with a variety of conven-
tional two-wire smoke detectors, four-wire smoke
detectors, and notification appliances. This includes Sys-
tem Sensor i3™ Series microprocessor-based detectors
with advanced features like drift compensation, mainte-
nance alert and freeze warning. (See Appendix A of the
Flex 410 Installation & Operations Manual PN 151321 for a
list of compatible devices.)
Outputs include four Class B (Style Y) or two Class A
(Style Z) supervised notification appliance circuits (NACs)
to annunciate alarm conditions. NAC circuits support single
circuit synchronization, regulated. Three programmable
auxiliary relay outputs can be programmed to activate (for
all zones or individual zones): pre-alarm, fire alarm, auxil-
iary alarm, alarm by zone and system or circuit troubles
(e.g., loss of AC, low battery, communication failure, phone
line trouble, fire drills, and NAC trouble).
The Flex 410 includes a built-in digital alarm communicator
(DACT) to report status to a central station. A user-friendly,
two-line LCD display and tactile keypad makes system pro-
gramming and control easy. The Flex 410 cabinet can be
flush- or surface-mounted and a Plexiglas window/dead-
front door kit is available where jurisdictions require. The
fully regulated, efficient 6-amp power supply with charger
ensures adequate power is available at all times.
The Flex 410 fire alarm control panel is listed to UL®
Standard 864, 9th Edition.
i 3™ is a trademark of Honeywell International Inc.
UL® is a registered trademark of Underwriter’s Laboratories, Inc.
Windows® is a registered trademark of Microsoft Corporation.
Features
GWF410
• 10 Class B (Style B) or 5 Class A (Style D) initiating
device circuits (IDCs), expandable up to 30 Class B or
15 Class A IDCs with optional zone expander(s)
• Supervised zone expanders and I/O modules can be
mounted remotely in optional accessory cabinet
• All zones compatible with 2- and 4-wire detectors
• Built-in digital alarm communication transmitter (DACT)
with dual phone line monitors
• 4 Class B (Style Y) or 2 Class A (Style Z) supervised
notification appliance circuits (NACs)
• Selectable/programmable NAC output patterns:
- ADA compliant strobe synchronization
- ANSI audible signals as required by NFPA 72
- Single Stroke BI
- Constant output
- California code
- March code
(continued next page)
An ISO 9000-2000 Company
SIGNALING
S521 7165-1288:182
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9021-60294 Rev. A page 1 of 2